Installation

10 - 1 Installation method

RZQS71-140DV1
A. Non stacked installation
1
10
B. Stacked installation
1. Obstacles exist in front of the outlet side
C. Multiple-row installation
1. Installation of one unit per row
31
• Outdoor Units • R-410A • RZQS-DV1
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit's drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
Relation of dimensions of H, A, and L are shown in the
table below.
L
0 < L ≤ 1/2 H
L ≤ H
1/2 H < L
H < L
Installation impossible
• Split Sky Air • Outdoor Units
2. Obstacles exist in front of the air inlet
2. Installing multiple units (2 units or more) in lateral
connection per row
A
150 (250)
200 (300)
Legend
Suction side obstacle
Discharge side obstacle
Left side obstacle
Right side obstacle
Top side obstacle
Obstacle is present
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.
In these cases, only 2 units can be
installed.
This situation is not allowed.
Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.