Installation; Upflow Installation; Bottom Return Air Inlet; Side Return Air Inlet - Carrier 58CVA Installation, Start-Up, Operating And Service And Maintenance Instructions

Table of Contents

Advertisement

AIR
DUCTS
INTERIOR
HEATED
SPACE
AIR DUCTS
* Minimum opening size is 100 sq in. with
minimum dimensions of 3 in.
Minimum of 3 in. when type-B1 vent is used.
Fig. 7—Confined Space: Air for Combustion and
Ventilation from an Unconfined Indoor Space
space and not less than the sum of the areas of all vent
connectors in the confined space. Equipment clearances to
the structure shall be at least 1 in. from the sides and back
and 6 in. from the front of the appliances. (See Table 2 and
Fig. 8.)
When ducts are used, they must be of the same cross sectional area
as the free area of the openings to which they connect. The
minimum dimension of ducts must not be less than 3 in.

INSTALLATION

Step 1—Upflow Installation

BOTTOM RETURN AIR INLET

These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler
panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.

SIDE RETURN AIR INLET

These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. This panel MUST be in place when
only side return air is used.
VENT THROUGH ROOF
12" MAX
1 SQ IN.
PER 1000
BTUH * IN DOOR
OR WALL
UNCONFINED
SPACE
6 " MIN
(FRONT)
1 SQ IN.
PER 1000
BTUH * IN DOOR
OR WALL
12" MAX
A02038
8
DUCTS
TO
OUTDOORS
12 " MAX
1 SQ IN.
A
PER 2000
BTUH *
AIR
DUCTS
DUCTS
TO
OUTDOORS
1 SQ IN.
B
PER 2000
BTUH *
12 " MAX
AIR DUCTS
* Minimum dimensions of 3 in.
NOTE:
Use any of the following
combinations of openings:
A & B
C & D
D & E
Fig. 8—Confined Space: Air for Combustion and
Ventilation from Outdoors
NOTE: Side return-air openings can be used in UPFLOW and
most HORIZONTAL configurations. Do not use side return-air
openings in DOWNFLOW configuration.

LEVELING LEGS (IF DESIRED)

In upflow position with side return inlet(s), leveling legs may be
used. (See Fig. 10.) Install field-supplied, 5/16 X 1 1/2 in. (max)
corrosion-resistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used.
It may be necessary to remove and reinstall bottom closure panel
to install leveling legs. To remove bottom closure panel, see Step
1 above.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each
bottom corner of furnace. (See Fig. 10.)
2. For each leg, install nut on bolt and then install bolt and nut in
hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat
washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside
nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
1 SQ IN.
PER 4000
BTUH *
D
12"
MAX
VENT
THROUGH
F
ROOF
1 SQ IN.
PER
4000
BTUH*
1 SQ IN.
PER
4000
BTUH*
E
G
12"
MAX
C
12 " MAX
DUCT
1 SQ IN.
TO
PER 4000
OUTDOORS
BTUH *
F & G
A02165