Installation - Carrier Minor 2 Series Installation, Start-Up, Operating And Service And Maintenance Instructions

80% afue, single stage, ecm motor, ultra low nox, 4-way multipoise, non-condensing, gas furnace
Table of Contents

Advertisement

58SU0A: Installation, Start-up, Operating and Service and Maintenance Instructions
If:
I
other = combined input of all other than fan-assisted appliances
in Btuh/hr
I
fan = combined input of all fan-assisted appliances in Btuh/hr
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and to the
Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if:
a. There are no closeable doors between rooms.
b. Combining spaces on same floor level. Each opening shall have
free area of at least 1 in.2/1,000 Btuh (2,000 mm2/kW) of the
total input rating of all gas appliances in the space, but not less
than 100 in.2 (0.06 m2). One opening shall commence within
12" (300 mm) of the ceiling and the second opening shall
commence within 12" (300 mm) of the floor. The minimum
dimension of air openings shall be at least 3 in. (80 mm), see
Fig.
8.
c. Combining space on different floor levels. The volumes of
spaces on different floor levels shall be considered as
communicating spaces if connected by one or more permanent
openings in doors or floors having free area of at least 2
in.2/1,000 Btuh (4,400 mm2/kW) of total input rating of all gas
appliances.
2. An attic or crawlspace may be considered a space that freely
communicates with the outdoors provided there are adequate
permanent ventilation openings directly to outdoors having free
area of at least 1-in.2/4,000 Btuh of total input rating for all gas
appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, infiltration
should be adequate to provide air for combustion, permanent
ventilation and dilution of flue gases. However, in buildings with
unusually tight construction, additional air MUST be provided
using the methods described in the Outdoor Combustion Air
Method section.
Unusually tight construction is defined as construction with:
a. Walls and ceilings exposed to the outdoors have a continuous,
sealed vapor barrier. Openings are gasketed or sealed and
b. Doors and openable windows are weatherstripped and
c. Other openings are caulked or sealed. These include joints
around window and door frames, between sole plates and floors,
between wall-ceiling joints, between wall panels, at penetrations
for plumbing, electrical and gas lines, etc.
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with the Indoor Combustion Air
Method below and,
2. Outdoor openings shall be located as required in the Outdoor
Combustion Air Method mentioned previously and,
3. Outdoor openings shall be sized as follows:
a. Calculate the Ratio of all Indoor Space volume divided by
required volume for Indoor Combustion Air Method below.
b. Outdoor opening size reduction Factor is 1 minus the Ratio in a.
above.
c. Minimum size of Outdoor openings shall be the size required in
Outdoor Combustion Air Method above multiplied by reduction
Factor in b. above. The minimum dimension of air openings shall
be not less than 3 in. (80 mm).
2. For each leg, install nut on bolt and then install bolt and nut in hole.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

INSTALLATION

UPFLOW INSTALLATION
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove two screws holding bottom filler
panel, see
Fig.
9.
Bottom
Closure Panel
Bottom Filler Panel
Fig. 9 – Removing Bottom Closure Panel
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. This panel MUST be in place when only side return
air is used.
NOTE: Side return-air openings can be used in UPFLOW and most
HORIZONTAL configurations. Do not use side return-air openings in
DOWNFLOW configuration.
Leveling Legs (If Desired)
In upflow position with side return inlet(s), leveling legs may be used,
see
Fig.
10. Install field-supplied, 5/16 x 1-1/2 in. (8 x 38 mm) (max)
corrosion-resistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used. It
may be necessary to remove and reinstall bottom closure panel to install
leveling legs. To remove bottom closure panel, see Item 1. in Bottom
Return Air Inlet section.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom
corner of furnace, see
Fig.
5/ 16
(8mm)
3
1
/
4
(44mm)
(8mm)
5
/
16
(44mm)
(44mm)
Fig. 10 – Leveling Legs
(Install flat washer if desired.)
8
10.
(8mm)
5/ 16
3
1
/
4
(44mm)
(8mm)
5/ 16
1
3/ 4
3/ 4
1
A10273
A89014

Advertisement

Table of Contents
loading

This manual is also suitable for:

Minor 3 series58su0a

Table of Contents