Part 6 - Wiring; Installation Must Comply With; Field Wiring Terminations; Field Wiring - Westinghouse WBMC**500 Manual

Installation start-up maintenance parts warranty commercial gas-fired boilers
Table of Contents

Advertisement

2. PVC or CPVC pipe should be the only material used for
condensate line. Steel, brass, copper, and other metals will be
subject to corrosion or deterioration.
3. A frozen condensate line could result in a blocked vent
condition. It is very important to protect the condensate
line from freezing temperatures or any type of blockage.
In installations that may encounter sustained freezing
conditions, the use of heat tape is recommended to avoid
freezing of the condensate line. It is also recommended to bush
up the condensate line size to 1" and terminate condensate
discharge as close to the unit as possible. Longer condensate
runs are more prone to freezing. Damages due to frozen or
blocked condensate lines ARE NOT covered by warranty.
4. Support of the condensate line may be necessary to avoid
blockage of the condensate flow.
5. To allow proper drainage on longer horizontal condensate
runs, tubing size may need to increase to 1" and a second line
vent may be required.
NOTE: To clean out condensate trap, see Maintenance
section.
The condensate line must remain unobstructed. If allowed
to freeze in the line or obstructed in any other manner,
condensate can exit from the boiler tee, resulting in potential
water damage to property. When installing a condensate
pump, select one approved for use with condensing boilers
and furnaces. The condensate pump should have an overflow
switch to prevent property damage from spillage. Condensate
from the boiler will be slightly acidic (pH from 3.2 to 4.5).
Install a neutralizing filter if required by local codes.
Is is very important that condensate piping be no smaller
than 3/4". Use a tee at the condensate connection with a
branch vertically up and open to the atmosphere to prevent a
vacuum that could obstruct the flow of condensate from the
boiler. To prevent sagging and maintain pitch, condensate
piping should be supported with pipe supports.
When installing a condensate pump, select one approved for
use with condensing boilers and furnaces. The pump should
have an overflow switch to prevent property damage from
condensate spillage.
Power to the optional condensate pump is continuous. When
the boiler is powered off the condensate pump will remain on.
It is important to remember to turn off the condensate pump
when powering down the boiler. Failure to do so could result
in property damage, severe personal injury, or death.

Part 6 - Wiring

To avoid electrical shock, turn off all power to the boiler prior
to opening an electrical box within the unit. Ensure the power
remains off while any wiring connections are being made.
Failure to follow these instructions could result in component
or product failure, serious injury, or death. Such product
failure IS NOT covered by warranty.
Jumping out control circuits or components WILL VOID
product warranty and can result in property damage, personal
injury, or death.
It is of extreme importance that this unit be properly grounded. It
is very important that the building system ground is inspected by
a qualified electrician prior to making this connection. Electrical
power must only be turned on when the boiler is completely
filled with cold water. Failure to follow these instructions could
result in component or product failure, serious injury, or death.
Electrical Shock Hazard - Turn off electrical power supply at
service entrance panel before making any electrical connections.
Failure to follow do do so could result in serious injury, or death.
Label all wires prior to disconnecting them when servicing
the boiler. Wiring errors can cause improper and dangerous
operation. Failure to follow these instructions may result in
property damage or personal injury.
Wiring must be NEC Class 1. If original wiring supplied with the
boiler must be replaced, use only TEW 105
Boiler must be electrically grounded as required by the National
Electrical Code, ANSI/NFPA 70 - Latest Edition.
A. Installation Must Comply With
1. National Electrical Code and any other national, state,
provincial, or local codes or regulations.
2. In Canada, CSA C22.1, Canadian Electrical Code Part 1, and
any local codes.
B. Field Wiring
Terminations
All connections made
to the boiler in the
field are done inside
the electrical junction
box located on the
left side of the unit.
Multiple
knockout
locations are available
to route field wires
into and out of the
electrical
junction
box.
Figure 22 - Knockout Locations
C. Field Wiring
All connections made to the boiler in the field are done inside
the electrical junction box located on the side of the unit. The
electrical junction box is located on the left side of the boiler.
Multiple knockout locations are available to route field wires
into and out of the electrical junction box.
The control used in this series of boilers is capable of directly
controlling 2 pumps when in standard mode and 3 pumps when
configured as a cascade master boiler. When configured as a
standard unit, each pump output can provide a maximum of 3
amps at 120 volts. If pumps used require more than this amount
of power, an external contactor or motor starter is needed. If
the boiler is configured as a cascade master, the system pump
output is a dry contact output capable of switching 5 amps at
120 volts in addition to the boiler pump and DHW pump outputs
sourcing 3 amps each.
The electrical junction box has separate, clearly marked terminal
strips for line voltage and low voltage wiring. Special jacks
31
o
C wire or equivalent.
WHL-033 Rev. 1.29.16