LG LAN090HSV Data Book page 75

Inverter single wall mounted
Hide thumbs Also See for LAN090HSV:
Table of Contents

Advertisement

Installation
How to connect wiring to the
terminals
◼ For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting
pliers, then strip the insulation to expose the strand
wiring about 10mm(3/8in).
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using a round terminal fastener or pliers, securely
clamp each stripped wire end with a round terminal.
(4) Position the round terminal wire, and replace and
tighten the terminal screw using a screwdriver.
According to the confirmation of the above conditions, prepare the wiring as follows.
1. Never fail to have an individual power circuit specifically for the air conditioner. As for the method of
wiring, be guided by the circuit diagram posted on the inside of control cover.
2. The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to
which the unit is subjected during the course of transportation. Check them and make sure that they are all
tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3. Specification of power source.
4. Confirm that electrical capacity is sufficient.
5. See that the starting voltage is maintained at more than 90 percent of the rated voltage marked on
the name plate.
6. Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.
7. Always install an earth leakage circuit breaker in a wet or moist area.
8. The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal
function of the overload.
9. The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an
air gap contact separation of at least 3mm in each active(phase) conductors.
74
Loosening the
terminal block
screw
Connecting cable
Inverter Single
Inverter Single
Inverter Single
Inverter Single
Power supply cable
Strand wire
Round
terminal
Connecting cable
Fastening the
wire tightly
6RMI0-02A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents