Low-Heat Only Installation - Carrier 58MVP Installation, Start-Up, And Operating Instructions Manual

Variable-capacity condensing gas furnace
Table of Contents

Advertisement

MIN
1
"
4
TO
1
" MAX
2
Fig. 11—Proper Condensate Drainage
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in fire, personal
injury, or death.
Do not install furnace on its back. (See Fig. 12.) Safety
control operation will be adversely affected. Never connect
return-air ducts to back of furnace.
UNIT DAMAGE HAZARD
This gas furnace may be used for construction heat provided
that:
-The furnace operating conditions, including ignition, input
rate, temperature rise and venting, are verified per instruc-
tions in this manual
-The furnace is permanently installed with all electrical
wiring, piping, venting and ducting installed according to
these installation instructions. A return air duct is provided,
sealed to the furnace casing, and terminated outside the space
containing the furnace. This prevents a negative pressure
condition as created by the circulating air blower, causing a
flame rollout and/or drawing combustion products into the
structure.
-The furnace is controlled by a thermostat. It may not be "hot
wired" to provide heat continuously to the structure without
thermostatic control.
-Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and other
construction materials. It also prevents the entrainment of
drywall dust into combustion air, which can cause fouling and
plugging of furnace components.
-The temperature of the return air to the furnace is no less
than 55°F, with no evening setback or shutdown. The use of
the furnace while the structure is under construction is
deemed to be intermittent operation per our installation
instructions.
-The air temperature rise is within the rated rise range on the
furnace rating plate, and the firing rate has been set to the
nameplate value.
-The filters used to clean the circulating air during the
construction process must be either changed or thoroughly
cleaned prior to occupancy.
-The furnace, ductwork and filters are cleaned as necessary to
remove drywall dust and construction debris from all HVAC
system components after construction is completed.
The furnace and its return air system shall be designed and
installed so that negative pressure created by the air circulating fan
cannot affect another appliance's combustion air supply or act to
mix products of combustion with circulating air, and that the air
circulating fan of the furnace, if installed in an enclosure commu-
nicating with another fuel-burning appliance not of the direct-vent
FRONT
HORIZONTAL
A04171
FRONT
BACK
FRONT
Fig. 12—Prohibit Installation on Back
type, shall be operable only when any door or panel covering an
opening in the furnace fan compartment or in a return air plenum
on ducts is in the closed position.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in minor property or
unit damage.
If these furnaces are installed in an unconditioned space
where ambient temperatures may be 32°F or lower, freeze
protection measures must be taken. (See Fig. 13.)
32 o F MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
Fig. 13—Freeze Protection
Step 2—Low-Heat Only Installation
This 58MVP furnace can be installed to operate in the low-heat
only heating mode when sized using the low-heat heating capacity.
This is accomplished by placing setup switch SW1-2 in the ON
position to provide only low-heat operation. With this setup,
high-heat operation will not occur. (See Fig. 25)
12
B
A
C
K
A93043
A93058

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents