Safety Devices - Waterstage WO*A060LDC Series Design & Technical Manual

Air to water split type
Table of Contents

Advertisement

91

SAFETY DEVICES

Current fuse
(Near the terminal)
Circuit protection
Current fuse
(Main PCB)
Thermal protection
Fan motor protection
program
Thermal protection program
(Compressor temp.)
Compressor protection
Thermal protection program
(Discharge temp.)
Thermal protection program
(Heat exchanger temp.)
High pressure protection
Pressure sensor
Low pressure protection
Pressure sensor
(Cooling mode only)
Protection from
WO A060LDC
250V 3.15A
- (OU01 - 25) -
Model
WO A080LDC
250V 20A
250V 25A
250V 15A
250V 10A
250V 3.15A
OFF: 100 ± 10 deg
ON: 95 ± 10 deg
OFF: 108 deg, ON: 80 deg
OFF: 110 deg, ON: After 7 minutes
OFF: 67 deg, ON: 63 deg
OFF: 4.2 Mpa, ON: 3.0 MPa
OFF: 0.12 Mpa, ON: 0.15 MPa
WO A100LDT
250V 25A
250V 3.15A
OFF: 150 ± 15 deg
ON: 120 ± 15 deg
Outdoor unit / Single phase