14
5
Place brass
washers onto
the faceplate hinge
bushing (2 extra
washers are sup-
plied in order to level
the doors if needed).
To remove the doors, open them slightly and lift them out of
the faceplate hinge bushings.
A raised hearth together with the fireplace built on a raised
platform is recommended for easier wood loading and fire
viewing.
The diameter of the chimney is 8".
A chimney venting the fireplace shall not vent any other
appliance.
The minimum overall chimney height from the top of
the fireplace is 15 feet.
The maximum overall chimney height from the top of
the fireplace is 34 feet.
Factory-built chimney systems for use in dwellings
constructed for three or more families must be enclosed
above the room in which the fireplace is located. This
enclosure must have a fire resistance rating equal to or
greater than that of the floor or roof assembly through
which they pass.
If the chimney system is enclosed within the attic area,
a rafter radiation shield is required.
The chimney should not be built with an offset angle in
excess of 45° in Canada and 30° in USA.
The chimney must extend at least 3 feet above its point
of contact with the roof and at least 2 feet higher than
any wall, roof or building within 10 feet.
W415-0594 / A / 02.15.07
Slide the door hinge pin
into the faceplate hinge
bushing.
CHIMNEY INSTALLATION
6
Install the air
c o n t r o l
threaded
rod
and knob.
If the chimney extends more than 5 feet above the roof,
it must be secured using a roof brace or guide wires.
Ensure that minimum clearances are maintained.
Portions of the chimney that extend through accessible
spaces must always be encased to avoid personal
contact with the chimney and thereby avoid damage to
the chimney.
A raincap must be installed to avoid internal damage
and corrosion.
The chimney must be supported at a maximum of 20
foot intervals (approx. 200 lbs/20 ft).
This fireplace was tested to CAN /ULC S610 Standard for
Factory Built Fireplaces, and to UL 127 Factory Built
Fireplaces. This Factory Built Fireplace is certified to burn
Fire Wood. The Factory Built Fireplace model: NZ6000
has met test criteria for Zero Clearance Installation to
Combustible Surfaces.
Any 8" diameter chimney listed to these standards may be
installed. In accordance with these standards, the unit may
also be connected to any chimney listed to CAN/ULC-S604
and CAN/ULC-S629 for Canada or UL-103HT for the United
States.
Installation of all types of factory-built chimney systems is
to be in accordance with the chimney manufacturers in-
stallation instructions. An appropriate chimney manufac-
turers anchor base plate and anchor base plate gasket is
required in order to initiate their system. Use the high tem-
perature gasket, supplied, to seal between the anchor plate
and the fireplace top. Air cooled chimney systems are not
recommended in colder climates.