Heatilator NEVO3630I-B Installation Manual page 38

Hide thumbs Also See for NEVO3630I-B:
Table of Contents

Advertisement

Install Horizontal Termination Cap (DVP and
SLP Pipe)
WARNING! Risk of Fire! The telescoping fl ue section of
the termination cap MUST be used when connecting vent.
• 1-1/2 (38 mm) minimum overlap of fl ue telescoping
section is required.
Failure to maintain overlap could cause overheating and
fi re.
• Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
• Flash and seal as appropriate for siding material at
outside edges of cap.
• When installing a horizontal termination cap, follow
the cap location guidelines as prescribed by current
ANSI Z223.1 and CAN/CGA-B149 installation codes
and refer to Section 4 of this manual.
Figure 7.16 Venting Through the Wall
Cap Specifi cation Chart (depth without using additional pipe sections)
DVP-TRAPK1
Top Vent Depth
4 1/2 to 6 3/8 in.
NEVO Series
DVP-HPC1
Top Vent Depth
4 1/2 to 6 5/8 in.
DVP-TRAP1 can adjust 1 1/2 in. (3 1/8 to 4 5/8)
DVP-TRAP2 can adjust 4 in. (5 3/8 to 9 3/8)
SLP-TRAP1 can adjust 1 5/8 in. (3 1/8 to 4 3/4)
SLP-TRAP2 can adjust 4 in. (5 1/4 to 9 1/4))
DVP-HPC1 can adjust 2 1/8 in. (4 1/4 to 6 3/8)
DVP-HPC2 can adjust 4 1/8 in. (6 3/8 to 10 1/2)
38
Wall Shield
Firestop
Inner Vent
Outer Vent
Vent depth from back of appliance to
outside surface of exterior wall
(see chart below)
DVP-TRAP1
Rear Vent Depth
3 to 4 7/8 in.
DVP-HPC1
Rear Vent Depth
3 to 5 1/8 in.
Heatilator • NEVO3630I-B, NEVO4236I-B Installation Manual • 2378-980 Rev. E • 4/16
CAUTION! Risk of Burns! Local codes may require in-
stallation of a cap shield to prevent anything or anyone
from touching the hot cap.
NOTICE: For certain exposures which require superior
resistance to wind-driven rain penetration, a fl ashing kit
and HRC caps are available. When penetrating a brick
wall, a brick extension kit is available for framing the brick.
Note: When using termination caps with factory-supplied
heat shield attached, no additional wall shield fi restop is
required on the exterior side of a combustible wall.
Heat Shield or
Heat Shield
Extended
1-1/2 in. (38 mm) min.
Heat Shield
Slip Section
can be extended
SHEATHING
INTERIOR
DVP-TRAPK2
DVP-TRAP2
Top Vent Depth
Rear Vent Depth
6 7/8 to 10 7/8 in.
5 3/8 to 9 3/8 in.
DVP-HPC2
DVP-HPC2
Top Vent Depth
Rear Vent Depth
6 5/8 to 10 3/4 in.
5 1/8 to 9 1/4 in.
overlap
EXTERIOR
SLP-TRAP1
Top Vent Depth
Top Vent Depth
2 to 3 7/8 in.
SLP-TRAP2
4 3/8 to 8 3/8 in.