Single stage operation oil burner

Advertisement

Available languages

Available languages

Installation, use and maintenance instructions
Instructions pour installation, utilisation et entretien
Single stage operation oil burner
GB
Brûleur à huile à une allure
F
RETROFIT APPLICATIONS ONLY
If this burner is being installed in a packaged unit (ie. burner comes with a boiler or furnace), follow the in-
stallation and set-up instructions supplied with the heating unit, as settings may differ from those shown in
WARNING
this manual.
- The following pages contain information, descriptions and diagrams for the proper installation and wir-
ing of the burner. Please read carefully before attempting final installation.
- This manual is to remain with the final installation designation. It is the installer's responsibility to ensure
that the burner installation and operation instructions mentioned in this manual are followed and operated
within local code authority limits.
POUR APPLICATIONS DE MISE À NIVEAU UNIQUEMENT
Si ce brûleur doit être installé avec un autre appareil avec lequel il est livré (comme une chaudière ou un
four), il faudra suivre la notice livrée avec l'unité chauffante dans la mesure où les instructions peuvent dif-
ATTENTION
férer de celles reportées dans ce manuel.
- Les pages qui suivent contiennent toutes les informations, descriptions et schémas permettant une ins-
tallation et un branchement approprié du brûleur. Veuillez lire attentivement ce manuel avant de procé-
der à l'installation de l'appareil.
- Ce manuel doit être conservé par l'utilisateur de l'appareil. L'installateur doit veiller à ce que les instructions
pour l'installation et le fonctionnement du brûleur reportées dans ce manuel soient respectées et appliquées
selon la loi du pays d'installation de l'appareil.
CODE
3726412
MODEL - MODÈLE
F15
WITH HYDRAULIC JACK
F15
AVEC VÉRIN HYDRAULIQUE
TYPE
264T
2902452 (9) - 06/2018

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the F15 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Riello F15

  • Page 1 Installation, use and maintenance instructions Instructions pour installation, utilisation et entretien Single stage operation oil burner Brûleur à huile à une allure RETROFIT APPLICATIONS ONLY If this burner is being installed in a packaged unit (ie. burner comes with a boiler or furnace), follow the in- stallation and set-up instructions supplied with the heating unit, as settings may differ from those shown in WARNING this manual.
  • Page 3 INSTALLLATION PRECAUTIONS WARNING AIR FOR COMBUSTION Do not install burner in room with insufficient air for combustion. Be sure there is an adequate air supply for combustion if the boiler/furnace room is enclosed. It may be necessary to create a window to permit suffi- cient air to enter the boiler/furnace room.
  • Page 4: Table Of Contents

    TABLE OF CONTENTS PACKAGE CONTENTS LIST ..............1 SERIAL NUMBER IDENTIFICATION .
  • Page 5: Package Contents List

    PACKAGE CONTENTS LIST Your Riello 40 burner should include the following parts. Please check to make sure all parts are present before begin- ning the installation. Quantity Description Code Burner chassis with cover 3726412 Universal mounting flange + mounting gasket...
  • Page 6: Technical Data

    450 Watts Motor (rated) 3250 rpm Run Current 4 AMP Capacitor 16 Microfarads 260V Pump pressure 100 to 200 psi Primary control RIELLO 530 SE/C Ignition transformer 8kV 16mA D8860 BURNER AND MOUNTING FLANGE DIMENSIONS Model Inches 11 3/4 13 25/32...
  • Page 7: Initial Set-Up

    INITIAL SET-UP A) Remove burner and air tube from cartons. Check parts list (inside cover) to ensure all parts are present. B) Remove burner cover by loosing the three screws securing it. Remove control box and air tube cover. C) Remove drawer assembly from air tube, insert nozzle and set Turbulator adjustment for specific input required, then set aside.
  • Page 8: Method 2-Semi-Flange Collar

    A) Insert the two BOLTS (1) into the UNIVERSAL MOUNTING FLANGE (10) from the flat side, ensuring the bolt heads are flush with the flat surface. Secure in place using two special CHROME NUTS (2) provided. B) Position the MOUNTING GASKET (3) between the flat surface of the UNIVERSAL MOUNTING FLANGE (10) and the appliance.
  • Page 9: Electrical Connections

    ELECTRICAL CONNECTIONS It is advisable to leave the control box off the sub-base while completing the electrical connection to the burner. 1) Wire access hole (Use BX electrical connector) 2) Earth ground conductor terminal (Green wire) 3) Hot conductor terminal (Black wire) 4) Neutral conductor terminal (White wire) Strain relief clamp WARNING:...
  • Page 10: Nozzle Placement

    NOZZLE PLACEMENT A) Determine the proper firing rate for the boiler or furnace units, considering the specific application, and then use the Burner Setup Charts to select the proper nozzle and pump pressure to obtain the required input from the burner. B) Remove the NOZZLE ADAPTER (2) from the DRAWER ASSEMBLY by loosening the SCREW (1).
  • Page 11: Oil Line Connections

    All pump port threads are British Parallel Thread design. Direct connection of NPT threads to the pump will dam- age the pump body. Riello manometers and vacuum gauges do not require any adaptors, and can be safely connected to the pump ports. An NPT (metric) adapter must be used when connecting other gauge models.
  • Page 12: Two Line (Lift System)

    Be sure that the plug in the RETURN PORT (9) is tightened securely. TWO LINE (LIFT SYSTEM) 2 LINE (LIFT) SYSTEM - PIPE LENGTHS 3/8” OD 1/2” OD D6008 NOTE: Do not exceed pipe lengths indicated in chart. A) If a two line system is required, install the By-pass plug (4) provided. The by-pass plug is installed in the return port (9) of the pump.
  • Page 13: Pump Purge

    PUMP PURGE NOTE: to protect the pump gears, it is advisable to lubricate the pump prior to purging a lift system. Apply oil through the VACUUM PORT (C). A) SINGLE LINE (GRAVITY FEED SYSTEM) A) Loosen the bleeder valve (A) until oil flows out. Tighten the bleeder valve securely and start burner. B) When bleeding the pump by pressure.
  • Page 14: Setting The Air Adjustment Plate

    SETTING THE AIR ADJUSTMENT PLATE A) The hydraulic AIR SHUTTER (1) is operated by the HYDRAULIC JACK (6), assuring complete opening of the combustion air intake. Regulation of the combustion air flow is made by adjustment of the manual AIR ADJUSTMENT PLATE (4) after loosening the FIXING SCREWS (3 &...
  • Page 15: Ducted Combustion Air Intake Applications

    Use a 4” to 6” pipe adapter (not supplied in the kit) to use a 6” diameter pipe. The settings of the burner must be according to the BURNER SETUP CHART – AIR INTAKE APPLICATIONS below. MODEL F15 BURNER SETUP CHART with 4" diameter pipe 20 Ft.
  • Page 16: Burner Start-Up Cycle

    COMBUSTION CHAMBER Follow the instructions furnished by the boiler/furnace manufacturer. Size retrofit application according to the appropriate installation codes (eg. CSA B139 or NFPA #31). BURNER START-UP CYCLE Normal Lock-out, due to light-failure Thermostat Motor Ignition transformer Valve Flame Lock-out lamp D5229 ~ 12 s ~ 12 s...
  • Page 17: Exploded Spare Parts List

    EXPLODED SPARE PARTS LIST 2902452...
  • Page 18: Spare Parts List

    SPARE PARTS LIST CODE DESCRIPTION CODE DESCRIPTION 3006911 HYDRAULIC JACK 3020304 ADAPTOR 3007816 CAPILLARY TUBE 3020301 OIL LINE 3000880 HYDRAULIC AIR SHUTTER 3020303 ADAPTOR AND NUT 3005799 3020302 BRACKET 5 20087024 CAPACITOR 16 μF 3006994 PIPE CONNECTOR - RETURN OPTIONAL 3005847 1/4”...
  • Page 19: Burner Start-Up Report

    BURNER START-UP REPORT Model number: Serial number: Project name: Start-up date: Installing contractor: Phone number: LIGHT OIL OPERATION : Low Fire Oil supply pressure: High Fire : Low Fire Oil suction pressure: High Fire Control Power Supply: CO: Low Fire High Fire : Low Fire Burner Firing Rate:...
  • Page 21 PRÉCAUTIONS POUR L'INSTALLATION PRÉCAUTION AIR POUR COMBUSTION Ne pas installer le brûleur dans une salle n'ayant pas assez d'air pour la combustion. Assurez-vous qu'il y ait une ali- mentation en air adéquate pour la combustion si la salle de la chaudière/four est encastrée. Il peut être nécessaire de créer une fenêtre pour permettre à...
  • Page 22 INDEX CONTENU DE L'EMBALLAGE ..............1 IDENTIFICATION DU NUMÉRO DE SÉRIE .
  • Page 23 CONTENU DE L'EMBALLAGE Votre brûleur Riello 40 doit être composé des pièces suivantes. Veuillez contrôler la présence de toutes les pièces énu- mérées ci-après avant de procéder à l'installation de l'appareil. Quantité Description Code Châssis brûleur avec capot 3726412 Bride de montage universelle + joint de montage 2567395 Sachet de pièces...
  • Page 24 3250 tours/min. Courant de cycle 4 AMP Condensateur 16 Microfarads 260V Pression de la pompe 100 à 200 psi Commande primaire RIELLO 530 SE/C Transformateur d'allumage 8kV 16mA D8860 DIMENSIONS DU BRÛLEUR ET DE LA BRIDE DE MONTAGE Modèle Pouces...
  • Page 25 PRÉPARATION A) Enlever le brûleur et le tube d'air des cartons. Contrôler que toutes les pièces de la liste du contenu de l'emballage (à l'intérieur du capot) sont présentes. B) Enlever le capot du brûleur en desserrant les trois vis qui le fixent. Enlever la boîte de contrôle et le capot du tube d'air. C) Enlever le tiroir du tube d'air, insérer le gicleur et régler le turbulateur pour l'entrée spécifique souhaitée, puis mettre de côté.
  • Page 26 A) Insérer les deux BOULONS (1) dans la BRIDE DE MONTAGE UNIVERSELLE (10) depuis le côté plat, en s'assu- rant que les têtes de boulon sont à ras de la surface plane. Les solidariser à l'aide des deux ÉCROUS CHROMÉS (2) spéciaux livrés avec l'appareil.
  • Page 27 CONNEXIONS ÉLECTRIQUES Il est conseillé d'enlever la boîte de contrôle de la sous-base lors de la réalisation de la connexion électrique au brûleur. 1) Trou d'accès des câbles (Utiliser le connecteur électrique BX) 2) Borne de conducteur de masse à la terre (Câble vert) 3) Borne de conducteur chaud (Câble noir) 4) Borne de conducteur neutre (Câble blanc) Serre câble...
  • Page 28 INSTALLATION DU GICLEUR A) Déterminer la plage d'allumage appropriée pour la chau- dière ou le four, en tenant compte de l'application spéci- fique, puis utiliser les tableaux de paramétrage du brûleur afin de sélectionner le gicleur approprié et la pression de pompe pour obtenir l'entrée voulue du brûleur.
  • Page 29 Les manomètres et les vacuomètres Riello n'ont pas besoin d'adaptateurs et peuvent être branchés aux orifices de la pompe en toute sécurité. Les adaptateurs NPT (métriques) doivent être utilisés en cas de branchement d'autres mo- dèles de manomètre.
  • Page 30 S'assurer que le bouchon du RACCORD DE RETOUR (9) est serré à fond. DEUX TUYAUX (SYSTÈME DE RELEVAGE) LONGUEURS DE TUYAUX DU SYSTÈME À DEUX TUYAUX (RELEVAGE) 3/8” Diam. ext. 1/2” Diam. ext. D6008 REMARQUE: Ne pas dépasser les longueurs de tuyaux indiqués dans le tableau.
  • Page 31 PURGE DE LA POMPE REMARQUE: Afin de protéger les engrenages de la pompe, il est recommandé de lubrifier la pompe avant de purger le système de relevage. Huiler le RACCORD DE VIDE (C). A) LIGNE UNIQUE (SYSTÈME D'ALIMENTATION PAR GRAVITÉ) A) Desserrer le purgeur (A) jusqu'à...
  • Page 32 RÉGLAGE DE LA PLAQUE DE RÉGLAGE D'AIR A) Le VOLET D'AIR hydraulique (1) est actionné par le VÉRIN HYDRAULIQUE (6) en assurant l'ouverture complète de la prise d'air de combustion. La régulation du flux d'air de combustion est effectuée par ajustement de la PLAQUE DE RÉGLAGE D'AIR (4) après avoir desserré...
  • Page 33 Les réglages du brûleur doivent être effectués conformément aux spécifications figurant dans le TABLEAU DE RÉGLAGE DU BRÛLEUR – APPLICATIONS DE PRISE D'AIR ci-dessous. TABLEAU DE RÉGLAGE DU MODÈLE DE BRÛLEUR F15 avec tube d'un diamètre de 4”. 20 pieds.
  • Page 34 CHAMBRE DE COMBUSTION Respecter les instructions fournies par le fabricant de la chaudière/four. Adapter l'application de mise à niveau selon les codes d'installation appropriés (par exemple CSA B139 ou NFPA #31). CYCLE DE DÉMARRAGE DU BRÛLEUR Normal Blocage, dû à une anomalie d'éclairage Thermostat Moteur Transformateur...
  • Page 35 CATALOGUE ÉCLATÉ DES PIÈCES DÉTACHÉES 2902452...
  • Page 36 CATALOGUE DES PIÈCES DÉTACHÉES CODE DESCRIPTION N° CODE DESCRIPTION 3006911 VÉRIN HYDRAULIQUE 3020304 ADAPTATEUR 3007816 TUBE CAPILLAIRE 3020301 TUYAU D'HUILE 3000880 VOLET D'AIR HYDRAULIQUE 3020303 ADAPTATEUR ET ÉCROU 3005799 VENTILATEUR 3020302 BRIDE 5 20087024 CONDENSATEUR 16 μF 3006994 RACCORD DE TUYAU - RETOUR OPTION 3005847 ADAPTATEUR MÉTRIQUE 1/4”...
  • Page 37 RAPPORT DE DÉMARRAGE DU BRÛLEUR Numéro de modèle: Numéro de série: Nom du projet: Date de démarrage: Installateur: Numéro de téléphone: FONCTIONNEMENT AU FIOUL Pression d'alimentation : Débit réduit Haut débit du fioul: Pression d'aspiration : Débit réduit Haut débit du fioul: Alimentation du contrôle: CO: Débit réduit...
  • Page 40 RIELLO S.p.A. I-37045 Legnago (VR) Tel.: +39.0442.630111 http:// www.riello.com RIELLO BURNERS NORTH AMERICA http://www.riello.ca 35 Pond Park Road 2165 Meadowpine Blvd Hingham, Massachusetts, Mississauga, Ontario U.S.A. 02043 1-800-4-RIELLO Canada L5N 6H6 Subject to modifications - Sous réserve de modifications...