Two Line (Lift System) - Riello 40 F10 Installation & Operating Manual

Single stage operation oil burner with manual air shutter
Table of Contents

Advertisement

TWO LINE (LIFT SYSTEM)

D6008
A) If a two line system is required, install the By-pass plug (4) provided. The by-pass
plug is installed in the return port (9) of the pump. A 2.5 mm hexagonal key provided
with the by pass plug is to be used to install the plug. DO NOT use an inch size
hexagonal key, damage to the by-pass plug may result. When operating on a two line
system, supply and return lines should be the same diameter and both should extend
to the same depth inside the fuel tank. Be sure there are no air leaks or blockages
in the piping system.
Any obstructions in the return line will cause failure of the pump shaft seal. Do not
exceed the pipe lengths indicated in the tables.
To install the by-pass plug:
1) Remove the return plug (9).
2) Install the by-pass plug (4) using the 2.5 mm hexagonal key.
B) Attach the two PIPE CONNECTORS (5) to the pump SUPPLY and pump RETURN
PORTS (6 and 9). Attach the required piping to these two pipe connectors using the
NPT/METRIC ADAPTERS that are supplied with the burner.
WARNING: Pipe dope or Teflon tape are NOT to be used on any direct oil con-
nection to the fuel pump.
WARNING: The height "P" in Pipe Length charts on page 9 and 10 should not
exceed 13 feet (4 m).
WARNING: The vacuum should not exceed 11.44 inches of mercury.
IMPORTANT: An external, appropriately listed and certified oil filter must be
placed in the fuel line between the fuel tank and the burner pump.
2 LINE (LIFT) SYSTEM - PIPE LENGTHS
H
FT
M
0.0
0.0
1.5
0.5
3.0
1.0
5.0
1.5
6.5
2.0
9.5
3.0
11
3.5
NOTE: Do not exceed pipe lengths
indicated in chart.
F10 - 10
3/8" OD
1/2" OD
FT
M
FT
115
35
330
100
30
330
80
25
330
65
20
295
50
15
230
25
8
100
20
6
65
M
100
100
100
90
70
30
20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents