In this section the terms Sink and Source are used.
Sink: This terms refers to an output that switches to
ground to do work.
Switch
Source: This term will be used to refer to an output that is
switched to positive to do work.
Switch
1. CHOKE
To use this feature, connect the choke or compression
release solenoid to the battery positive and then to the
terminal or wire shown:
A88-F
Output
A88 Wire color
Terminal
Choke
No. 3
At the beginning of each crank cycle, the choke or
compression release solenoid will pull in, remain in for 3
or 4 seconds. The maximum current this circuit can carry
is 1 amp.
2. SUMMARY
For a remote shutdown or alarm feature after a shutdown
occurs, connect the alarm or lamp to the battery positive
then to the terminal or wires shown:
A88-F
Output
Terminal
Summary
No. 20
SECTION IV: OPTIONAL HOOKUPS
Lamp
Terminal
Lamp
Terminal
Output
Operation
Violet
Sink
A88
Output
Wire color
Operation
Sink
Brown
3. CRANK CONNECTIONS
A88-F
Terminal
A Crank
No. 1
B Crank
No. 2
If the crank solenoid is already connected to ground,
connect to the unit as indicated in "A" above.
If the crank solenoid is already connected to the battery
positive, connect it as in "B" above.
4. ENGINE RUNNING
If it is desirable to know or indicate when the engine is
actually running, connect the indicator to the battery
positive and then as below:
Output
Terminal
Engine
Running
After the engine has been running for approximately 30
Max.
seconds, the indicator will be energized.
Current
1 A
5. WARM UP
If it is desirable to have a warm up period or a 90 second
delay after the engine has started, connect the engine
running output to the time delay input and then connect
the time delay to the gas feed or clutch mechanism.
Terminal 18 to terminal 9 on the A88-F, the yellow wire to
the violet/white wire on the A88 unit.
Connect the clutch or gas feed solenoid to battery positive
then to the time delay output terminal 19 on the A88-F;
the orange wire on the A88.
After the engine starts and has been running for approx-
imately 90 seconds, the clutch or gas feed will be energized.
Max.
Current
1
/
A
2
4
A88 wire color
Connected
Solenoid
White/Brown
to Ground
Solen. to
White/Red
batt. pos.
A88-F
A88 Wire color
No. 18
Yellow
Output
Max.
Operation
Current
Source
1 A
Sink
Output
Max.
Operation
Current
After 30
1 A
sec. delay
Sink