Installation; External View - Toshiba RAV-SM564UT-E Installation Manual

Hide thumbs Also See for RAV-SM564UT-E:
Table of Contents

Advertisement

4-way Air Discharge Cassette Type
4

INSTALLATION

REQUIREMENT
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by
necessity, be sure to use buffering cloth, etc. to not damage the unit.
• To move the indoor unit, hold the hooking metals (4 positions) only.
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts, etc.).
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other
than specified.

External view

Ceiling bottom
surface
Ceiling bottom
surface
Knockout for
simple OA
For Ø100
Ceiling bottom surface
Model RAV
SM56 Type
SM80 Type
SM110 Type
Knockout square hole
for divide duct
For Ø150
840 Unit external dimension
Knockout square
hole for divide duct
For Ø150
690 ± 20 Hanging bolt pitch
860 to 910 Panel external dimension
950 Ceiling opening dimension
Z view
Ceiling panel (sold separately)
Knockout square hole for humidifier
A
B
C
256
Ø6.4
Ø12.7
256
Ø9.5
Ø15.9
319
Ø9.5
Ø15.9
Ceiling bottom surface
Electric parts
box
Knockout square hole
for divide duct
For Ø150
Hanging bolt M10 or Ø3/8
(To be procured locally)
Knockout square hole for divide duct
For Ø150
D
Model RAV
120
SM140 Type
120
SM160 Type
183
– 8 –
Installation Manual
(Unit:mm)
Refrigerant pipe
connecting port
(Liquid) B
Take-in port
Refrigerant pipe
of pipes
connecting port
(Gas) C
Drain pipe
connecting
port
Ceiling
bottom
surface
(mm)
A
B
C
D
319
Ø9.5
Ø15.9
183
319
Ø9.5
Ø15.9
183
EN
8-EN