Step 7 The Gas Supply Line; Step 8 Gas Pressure Requirements - Heat-N-Glo SL-350TV Installer's Manual

B-type vent gas fireplace
Table of Contents

Advertisement

STANDING PILOT
DSI IGNITION
CERAMIC
INSULATOR
1/4" (6mm)
Figure 8.
Gas Control Systems
Step 7. The Gas Supply Line
NOTE: Have the gas supply line installed by a qualified
service technician in accordance with all building codes.
NOTE: Before the first firing of the fireplace, the gas
supply line should be purged of any trapped air.
NOTE: Consult local building codes to properly size
the gas supply line leading to the 1/2 inch
(13 mm) hook-up at the unit.
This gas fireplace is designed to accept a 1/2 inch
(13 mm) gas supply line.
To install the gas supply line:
• A listed 1/2 inch (13 mm) manual shut-off valve and a
listed flexible gas connector are connected to the 1/2
inch (13 mm) inlet of the control valve.
• Locate the gas line access hole in the outer casing of
the fireplace.
• The gas line may be run from either side of the fireplace
provided the hole in the outer wrap does not exceed 2” in
diameter and it does not penetrate the actual firebox.
• Open the fireplace lower grille, insert the gas supply line
through the gas line hole, and connect it to the shut-off
valve.
• When attaching the pipe, support the control so that the
lines are not bent or torn.
IGNITOR
1/2" (13mm)
• After the gas line installation is complete, use a soap
solution to carefully check all gas connections for leaks.
WARNING: DO NOT USE AN OPEN FLAME
!
TO CHECK FOR GAS LEAKS.
• Insert insulation from the outside of the fireplace and
pack the insulation tightly to totally seal between the
pipe and the outer casing.
• At the gas line access hole the gap between the supply
piping and gas access hole can be plugged with non-
combustible insulation to prevent cold air infiltration.
Figure 9. Gas Supply Line
Step 8. Gas Pressure Requirements
Pressure requirements for Heat-N-Glo gas fireplaces
are shown in the table below.
Pressure
Minimum
Inlet Pressure
Maximum Inlet
Gas Pressure
Manifold
Pressure
A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is
provided on the inlet and outlet side of the gas control for a
test gauge connection to measure the manifold pressure.
The fireplace and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of the system at test pressures in
excess of one-half (1/2) psig (3.5 kPa).
The fireplace must be isolated from the gas supply piping
system by closing its individual shut-off valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than one-half (1/2) psig (3.5 kPa).
13
USE A WRENCH ON
SHUT-OFF VALVE WHEN
TIGHTENING GAS LINE
MANUAL
SHUT-OFF VALVE
GAS VALVE
CONNECTOR
Natural Gas
Propane
5.0 inches
11.0 inches
w.c.
w.c.
14.0 inches
14.0 inches
w.c.
w.c.
3.5 inches
10.0 inches
w.c.
w.c.
FLEX