2-3
OPTIONAL ACCESSORIES
• The optional decoration panel and remote controller are
required for this indoor unit. (Refer to Table 1)
• These are two types of remote controllers: wired and wire-
less. Select a remote controller from Table 2 according to
customer request and install in an appropriate place.
Table 1
Model
FXCQ20 · 25 · 32MVE
BYBC32GJW1 · BYBC32G-W1
FXCQ40 · 50MVE
BYBC50GJW1 · BYBC50G-W1
FXCQ63MVE
BYBC63GJW1 · BYBC63G-W1
FXCQ80 · 125MVE
BYBC125GJW1 · BYBC125G-W1
Table 2
Remote controller
Wired type
Wireless type
NOTE
• If the you wishes to use a remote controller that is not listed
above, select a suitable remote controller after consulting
catalogs and technical materials.
FOR THE FOLLOWING ITEMS, TAKE SPECIAL
CARE DURING CONSTRUCTION AND CHECK
AFTER INSTALLATION IS FINISHED.
a. Items to be checked after completion of work
If not properly done, what is
Items to be checked
likely to occur
Are the indoor and outdoor
The units may drop, vibrate
unit fixed firmly?
or make noise.
It may result in insufficient
Is the gas leak test finished?
cooling.
Is the unit fully insulated?
Condensate water may drip.
Does drainage flow
Condensate water may drip.
smoothly?
Does the power supply volt-
The unit may malfunction or
age correspond to that
the components burn out.
shown on the name plate?
Are wiring and piping cor-
The unit may malfunction or
rect?
the components burn out.
Dangerous at electric leak-
Is the unit safely grounded?
age.
Is wiring size according to
The unit may malfunction or
specifications?
the components burn out.
Is something blocking the air
It may result in insufficient
outlet or inlet of either the
cooling.
indoor or outdoor units?
Are refrigerant piping length
The refrigerant charge in the
and additional refrigerant
system is not clear.
charge noted down?
b. Items to be checked at time of delivery
Also review the "SAFETY PRECAUTIONS"
Items to be checked
Did you explain about operations while showing the
instruction manual to your customer?
Did you hand the instruction manual over to your cus-
tomer?
English
Optional decoration panel
White
Heat pump type
Cooling only type
Check
Check
c. Points for explanation about operations
The items with
WARNING and
in the instruction manual are the items pertaining to
possibilities for bodily injury and material damage in
addition to the general usage of the product. Accordingly, it
is necessary that you make a full explanation about the
described contents and also ask your customers to read the
instruction manual.
2-4
NOTES TO INSTALLER
Be sure to instruct customers how to properly operate the
unit (especially cleaning filters, operating different functions,
and adjusting the temperature) by having them carry out
operations themselves while looking at the manual.
3.

SELECTING INSTALLATION SITE

Please attach additional thermal insulation material to the unit
body when it is believed that the relative humidity in the ceiling
exceeds 80%. Use glass wool, polyethylene foam, or similar
with a thickness of 10 mm or more as thermal insulation mate-
rial.
(1) Select an installation site where the following condi-
tions are fulfilled and that meets with your
customer's approval.
• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate can be properly drained.
• In the upper space of the indoor unit where there is no
possible dripping of water from the refrigerant pipe, drain
pipe, water pipe, etc.
• If supporting structural members are not strong enough
to take the unit's weight, the unit could fall out of place
and cause serious injury.
• Where the false ceiling is not noticeably on an incline.
• Where there is no risk of flammable gas leakage.
• Where sufficient clearance for maintenance and service
can be ensured.
• Where piping between indoor and outdoor units is possi-
ble within the allowable limit. (Refer to the installation
manual for the outdoor unit.)
• Any vents, light fixtures, or other appliances which may
disturb the airflow might cause the top side to become
dirty if located too nearby, so follow the figure below when
installing.
• Install the indoor and outdoor units, power supply wiring
and connecting wires at least 1 meter away from televi-
sions or radios in order to prevent image interference or
noise.
(Depending on the radio waves, a distance of 1 meter
may not be sufficient enough to eliminate the noise.)
CAUTION marks