C. Constructing the Appliance Chase
A chase is a vertical box-like structure built to enclose the
gas appliance and/or its vent system. In cooler climates
the vent should be enclosed inside the chase.
NOTICE: Treatment of ceiling fi restops and wall shield
fi restops and construction of the chase may vary with the
type of building. These instructions are not substitutes
for the requirements of local building codes. Therefore,
you MUST check local building codes to determine the
requirements to these steps.
Chases should be constructed in the manner of all out-
side walls of the home to prevent cold air drafting prob-
lems. The chase should not break the outside building
envelope in any manner.
Walls, ceiling, base plate and cantilever fl oor of the chase
should be insulated. Vapor and air infi ltration barriers
should be installed in the chase as per regional codes for
the rest of the home. Additionally, in regions where cold
air infi ltration may be an issue, the inside surfaces may be
sheetrocked and taped (or an equivalent method may be
used) to achieve maximum air tightness.
B
D
DVP Pipe SLP Pipe
Models
Rough
Opening
(Width)
in.
10
SL-550TR-E
SL-550TR-IPI-E
mm
254
in.
10
SL-750TR-E
SL-750TR-IPI-E
mm
254
in.
10
SL-950TR-IPI-E
mm
254
* Adjust framing dimensions for interior sheathing (such as sheetrock)
C** Add 12 inches for rear venting with one 90° elbow.
Figure 3.6 Clearances to Combustibles
Heat & Glo • SL-550/750TR-E, SL-550/750/950TR-IPI-E Installation Manual • 2118-910 Rev. C • 4/16
A
C
*
MINIMUM FRAMING DIMENSIONS
A
B
**DVP Pipe SLP Pipe
Rough
Rough
Rough
Opening
Opening
Opening
(Height)
(Width)
(Depth)
8-5/8
34-3/4
16-1/4
219
883
413
8-5/8
38-1/4
16-1/4
219
971
413
8-5/8
42 1/4
16-1/4
219
1073
413
To further prevent drafts, the wall shield and ceiling fi re-
stops should be caulked with caulk with a minimum of
300ºF continuous exposure rating to seal gaps. Gas
line holes and other openings should be caulked with
caulk with a minimum of 300ºF continuous exposure rating
or stuffed with unfaced insulation. If the appliance is being
installed on a cement surface, a layer of plywood may be
placed underneath to prevent conducting cold up into the
room.
NOTICE: Install appliance on hard metal or wood surfaces
extending full width and depth. DO NOT install directly
on carpeting, vinyl, tile or any combustible material other
than wood.
WARNING! Risk of Fire! Maintain specifi ed air space
clearances to appliance and vent pipe:
• Insulation and other materials must be secured to prevent
accidental contact.
• The chase must be properly blocked to prevent blown
insulation or other combustibles from entering and
making contact with fi replace or chimney.
• Failure to maintain airspace may cause overheating and
a fi re.
F
J
G
C
D
E
Rough
Clearance
Rough
Opening
to Ceiling
Opening
(Width)
(Depth)
16-1/4
37
32
413
940
813
16-1/4
42
32
413
1067
813
16-1/4
49
32
413
1245
813
MEASURE FROM TOP OF
UNIT OPENING OR FROM
TOP OF HOOD
I
F
G
H
Combustible
Combustible
Behind
Floor
Flooring
Appliance
0
0
1/2
0
0
13
0
0
1/2
0
0
13
0
0
1/2
0
0
13
E
H
I
J
Sides of
Front of
Appliance
Appliance
1/2
36
13
915
1/2
36
13
915
1/2
36
13
914
13