16.5.26. Indoor Water Inlet Temperature Sensor Abnormality (F37)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the indoor water inlet temperature sensor are
used to determine sensor error.
Malfunction Caused:
1. Faulty connector connection.
2. Faulty sensor.
3. Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 5 seconds.
96