12.1.5. Setting Water Outlet Temperature For Heat Mode
• The set temperature define the parameters for the outdoor ambient temperature dependent operation of the unit. Where by the
internal water setting temperature is determined automatically depending on the outdoor temperature. The colder outdoor
temperatures will result in warmer water and vice versa. The user has the possibility to shift up or down the target water
temperature by control panel setting.
• Change in setting water outlet temperature is updated every 30 minutes.
12.1.5.1. Heating Mode Operation Time Chart
1. 3 ways valve control:
• 3 ways valve switch and fix to heating side
2. Heat pump operate follow normal heating operation.
3. Backup heater operate follow normal operation.
4. Solar 3 way valve operates follow solar operation specification.
12.1.6. Water Temperature Thermo Shift Setting
• Switchs are ignored during "PUMPDW" = ON.
• Switchs are ignored during "STATUS" = ON.
• "
", "
", "SELECT" switch are ignored if "SETTING" = OFF.
• "CANCEL" switch is ignored if "SETTING" = OFF & "STATUS" = OFF.
• If "SET" Switch pressed for less than 5secs, immediately enter water temperature shift setting mode.
• Once enter this setting mode, "SETTING" display is ON.
This setting mode is used to easily shift the target water outlet temperature.
Example
50