16.2. Relationship Between The Condition Of The Air-to-Water Heatpump
Indoor And Outdoor Units And Pressure And Electric Current
Heating Mode
Condition of the
Air-to-Water Heatpump indoor and outdoor
Low Pressure
High Pressure
Electric current during operation
units
Water leakage or insufficient water flow
rate in the system
Excessive amount of refrigerant
Inefficient compression
Insufficient refrigerant
(gas leakage)
Outdoor heat exchange deficiency
Clogged expansion valve or Strainer
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.