Error Codes Table - Panasonic CS-NE9LKE Service Manual

Indoor/outdoor unit
Hide thumbs Also See for CS-NE9LKE:
Table of Contents

Advertisement

15.3.

Error Codes Table

Diagnosis
Abnormality /
display
Protection control
H00
No memory of failure
H11
Indoor/outdoor
abnormal
communication
H14
Indoor intake air
temperature sensor
abnormality
H15
Compressor
temperature sensor
abnormality
H16
Outdoor current
transformer (CT)
abnormality
H19
Indoor fan motor
merchanism lock
H23
Indoor heat exchanger
temperature sensor 1
abnormality
H24
Indoor heat exchanger
temperature sensor 2
abnormality
H25
Indoor E-Ion
abnormality
H27
Outdoor air temperature
sensor abnormality
H28
Outdoor heat exchanger
temperature sensor 1
abnormality
H30
Outdoor discharge pipe
temperature sensor
abnormality
H33
Indoor / outdoor
misconnection
abnormality
H38
Indoor/Outdoor
mismatch (brand code)
H58
Indoor gas sensor
abnormality
H97
Outdoor fan motor
mechanism lock
H98
Indoor high pressure
protection
H99
Indoor operating unit
freeze protection
F11
4-way valve switching
abnormality
F90
Power factor correction
(PFC) circuit protection
F91
Refrigeration cycle
abnormality
Abnormality
Protection
Judgement
operation
Normal operation
After operation for
Indoor fan only
1 minute
operation can
start by entering
into force cooling
operation
Continuous for 5s
Continuous for 5s
Continuous
happen for 7 times
Continuous for 5s
Continuous for 5s
Port is ON for 10s
during E-Ion off
Continuous for 5s
Continuous for 5s
Continuous for 5s
Continuous for 6
hours
2 times happen
within 30 minutes
4 times happen
within 30 minutes
4 times happen
within 10 minutes
2 times happen
within 20 minutes
Problem
Indoor/outdoor
communication not establish
Indoor intake air temperature
sensor open or short circuit
Compressor temperature
sensor open or short circuit
Current transformer faulty or
compressor faulty
Indoor fan motor lock or
feedback abnormal
Indoor heat exchanger
temperature sensor 1 open
or short circuit
Indoor heat exchanger
temperature sensor 2 open
or short circuit
Outdoor air temperature
sensor open or short circuit
Outdoor heat exchanger
temperature sensor 1 open
or short circuit
Outdoor discharge pipe
temperature sensor open or
short circuit
Indoor and outdoor rated
voltage different
Brand code not match
Indoor gas sensor open or
short circuit
Outdoor fan motor lock or
feedback abnormal
Indoor high pressure
protection (Heating)
Indoor freeze protection
(Cooling)
4-way valve switching
abnormal
Power factor correction
circuit abnormal
Refrigeration cycle abnormal
52
Check location
• Indoor/outdoor wire terminal
• Indoor/outdoor PCB
• Indoor/outdoor connection wire
• Indoor intake air temperature
sensor lead wire and connector
• Compressor temperature sensor
lead wire and connector
• Outdoor PCB faulty or
compressor faulty
• Fan motor lead wire and
connector
• Fan motor lock or block
• Indoor heat exchanger
temperature sensor 1 lead wire
and connector
• Indoor heat exchanger
temperature sensor 2 lead wire
and connector
• E-Ion PCB
• Outdoor air temperature sensor
lead wire and connector
• Outdoor heat exchanger
temperature sensor 1 lead wire
and connector
• Outdoor discharge pipe
temperature sensor lead wire and
connector
• Indoor and outdoor units check
• Check indoor unit and outdoor
unit.
• Indoor gas sensor
• Indoor PCB
• Outdoor fan motor lead wire and
connector
• Fan motor lock or block
• Check indoor heat exchanger
• Air filter dirty
• Air circulation short circuit
• Check indoor heat exchanger
• Air filter dirty
• Air circulation short circuit
• 4-way valve
• Lead wire and connector.
• Outdoor PCB faulty
• Insufficient refrigerant or valve
close