SECTION 1.5
ENGINE-GENERATOR PROTECTIVE DEVICES

OVERCRANK SHUTDOWN

This feature prevents the generator from damaging
itself when it continually attempts to start and another
problem, such as no fuel supply, prevents it from start-
ing. The unit will crank and rest for a preset time limit.
Then, it will stop cranking, and the LED on the gen-
erator control panel will light indicating an overcrank
failure. The AUTO/OFF/MANUAL switch will need to
be set to OFF and then back to AUTO to reset the
generator control board.
NOTE: If the fault is not repaired, the overcrank
feature will continue to activate.
APPROXIMATE CRANK CYCLE TIMES:
7 KW UNITS:
15 seconds ON
7 seconds OFF
7 seconds ON
7 seconds OFF
7 seconds ON
7 seconds OFF
7 seconds ON
7 seconds OFF
7 seconds ON
7 seconds OFF
7 seconds ON
If the unit fails to start, the overcrank alarm LED will
be illuminated.
10 KW, 13 KW AND 16 KW UNITS:
16 seconds ON
7 seconds OFF
16 seconds ON
7 seconds OFF
7 seconds ON
7 seconds OFF
7 seconds ON
7 seconds OFF
7 seconds ON
7 seconds OFF
If the unit fails to start, the overcrank alarm LED will
be illuminated.
Page 24
PART 1
GENERAL INFORMATION