Power Cord Installation - Sears PG8MAA Installation, Start-Up And Service Instructions Manual

Single-stage deluxe induced-combustion 4-way multipoise gas furnace
Table of Contents

Advertisement

Table
6 --Electrical
Data
FURNACE
SIZE
VOLTS-
HERTZ-
PHASE
OPERATING
VOLTAGE
RANGE
MAXIMUM
UNIT AMPS
Maximum*
Minimum*
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
UNiT
AMPACITY#
045=08/024045
115-60-1
5.2
7.26
045=12/036045
115-60-1
7.2
9.79
070=08/024070
115-60-1
5.1
7.14
070=12/036070
115-60-1
7.2
9.72
070=16/048070
115-60-1
9.5
12.60
090=14/042090
115-60-1
8.6
11.39
090=16/048090
115-60-1
10.0
13.09
090 = 20/060090
115-60-1
14.1
18.2
110=12/036110
115-60-1
8.6
11.27
110=16/048110
115-60-1
10.2
13.34
110=22/066110
115-60-1
15.1
19.42
135=16/048135
115-60-1
10.5
13.63
135=22/066135
115-60-1
14.5
18.72
155=20/060155
115-60-1
15.4
19.83
MAXIMUM
WiRE
LENGTH FT.
(M)$
49
(14.9)
37
(11.2)
51 (15.5)
38 (11.5)
29 (8.8)
32 (9.7)
28 (8.5)
31 (9.4)
32 (9.7)
27 (8.2)
29 (8.8)
27 (8.2)
30 (9.1)
29 (8.8)
Permissible limits of the voltage
range at which the unit operates satisfactorily.
MAXIMUM
FUSE OR
MINIMUM
CKT BKR
WIRE
AMPSI"
GAUGE
15
14
15
14
15
14
15
14
15
14
15
14
15
14
20
12
15
14
15
14
20
12
15
14
20
12
20
12
# Unit ampacity
= 125 percent of largest operating
component's
full load amps plus 100 percent of all other potential
operating components'
(EAC, humidifier,
etc.) full load amps.
1- Time-delay
type is recommended.
Length shown is as measured
1 way along wire path between
unit and service panel for maximum 2 percent voltage drop.
12. Complete
electrical
box wiring
and installation.
Connect
line voltage
leads as shown
in Fig. 26. Use best practices
(NEC) for wire bushings,
strain relief, etc.
13. Reinstall
cover
to J-Box.
Do
not pinch
wires
between
cover and bracket.
POWER
CORD
INSTALLATION
IN FURNACE
J-BOX
NOTE:
Power
cords
must
be
able to handle
the electrical
requirements
listed
in
Table
6.
Refer
to
power
cord
manufacturer's
listings.
1. Remove
cover from J-Box.
2. Route listed power cord through
7/8-in.
(22 ram) diameter
hole in J-Box.
3. Secure
power
cord to J-Box
bracket
with
a strain
relief
bushing
or a connector
approved
for the type of cord used.
4. Secure field ground
wire to green ground
screw on J-Box
bracket.
5. Connect
line voltage
leads as shown
in Fig. 26.
6. Reinstall
cover
to J-Box.
Do
not pinch
wires
between
cover and bracket.
BX CABLE
INSTALLATION
IN FURNACE
J-BOX
1. Remove
cover from J-Box.
2. Route
BX cable into 7/8-inch
(22 ram) diameter
hole in
J-Box.
3. Secure
BX cable to J-Box
bracket
with
connectors
ap-
proved
for the type of cable used.
4. Secure field ground
wire to green ground
screw on J-Box
bracket.
5. Connect
line voltage
leads as shown
in Fig. 26.
6. Reinstall
cover
to J-Box.
Do
not pinch
wires
between
cover and bracket.
22