Fire Or Explosion - Sears PG8MAA Installation, Start-Up And Service Instructions Manual

Single-stage deluxe induced-combustion 4-way multipoise gas furnace
Table of Contents

Advertisement

f
1-7/8
(47.6 mm)
Fig. 47 -
Igniter
Position-Top
View
A05026
A01050
Fig. 48 -
Cleaning
Heat Exchanger
Cell
(4) Insert brush
end of cable in burner
inlet opening
of cell, and
proceed
to clean 2 lower passes
of cell in same manner
as upper
pass.
(5) Repeat
foregoing
procedures
until each cell in furnace
has
been cleaned.
(6) Using vacuum
cleaner, remove
residue from each cell.
(7) Using
vacuum
cleaner
with
soft
brush
attachment,
clean
burner
assembly.
(8) Clean flame sensor with fine steel wool.
(9) Install
NOx baffles
(if removed).
(10) Reinstall
burner
assembly.
Center burners
in cell openings.
10. Remove
old sealant
from
cell panel
and
collector
box
flange.
11. Spray
releasing
agent
on the heat exchanger
cell panel
where collector
box assembly
contacts
cell panel.
NOTE:
A releasing
agent
such as cooking
spray or equivalent
(must
not contain
corn
or canola
oil, aromatic
or halogenated
hydrocarbons
or inadequate
seal may
occur)
and RTV
sealant
(G.E.
162,
6702,
or Dow-Corning
738)
are
needed
before
starting
installation.
DO NOT
substitute
any other type of RTV
sealant.
G.E. 162 (P771-9003)
is available
through
RCD in 3-oz
tubes.
12. Apply
new sealant
to flange
of collector
box and attach to
cell panel
using
existing
screws,
making
sure all screws
are secure.
13. Reconnect
wires
to the following
components.
(Use con-
nection
diagram
on wiring
label, if wires were not marked
for reconnection
locations.):
a. Draft safeguard
switch.
b. Inducer
motor.
c. Pressure
switch(es).
d. Limit over-temperature
switch.
e. Gas valve.
f. Hot surface igniter.
g. Flame-sensing
electrode.
h. Flame rollout switches.
47
i. Install NOx baffles (if removed).
14. Reinstall
internal
vent pipe, if applicable.
15.
Reinstall
vent connector
on furnace
vent elbow. Securely
fasten vent connector
to vent elbow with 2 field-supplied,
corrosion-resistant,
sheet metal screws located
180 ° apart.
16. Replace
blower
access door only, if it was removed.
17. Set thermostat
above room temperature
and check furnace
for proper operation.
18. Verify blower
airflow
and speed changes
between
heating
and cooling.
FIRE
OR EXPLOSION
HAZARD
Failure
to follow
this warning
could
result
in personal
injury,
death and/or property
damage.
Never
test
for gas
leaks
with
an
open
flame.
Use
a
commercially
available
soap solution
made
specifically
for
the detection
of leaks to check
all connections.
A fire or
explosion
may
result
causing
property
damage,
personal
injury or loss of life,
19. Check for gas leaks.
20. Replace
outer access door.
Step 3 mSequence
of Operation
NOTE:
Furnace
control
must be grounded
for proper
operation
or
control
will
lock
out.
Control
is
grounded
through
green/yellow
wire
routed
to gas valve
and
manifold
bracket
screw.
Using the schematic
diagram
in Fig. 41, follow
the sequence
of
operation
through
the different
modes.
Read
and
follow
the
wiring diagram
very carefully.
NOTE:
If a power
interruption
occurs during
a call t\_r heat (W),
the
control
will
start
a 90-sec
blower-only
ON
period
two
seconds
after power
is restored,
if the thermostat
is still calling for
gas heating.
The amber
LED light will flash
code 12 during
the
90-sec
period,
after which
the LED
will be ON continuous,
as
long as no faults are detected.
After the 90-sec
period,
the furnace
will respond
to the thermostat
normally.
The blower
door must
be installed
for power
to be conducted
through
the
blower
door
interlock
switch
ILK to the furnace
control
CPU,
transformer
TRAN,
inducer
motor
IDM,
blower
motor BLWM,
hot-surface
igniter HSI, and gas valve GV.
1. Heating
(See Fig. 26 for thermostat
connections.)
The wall thermo-
stat "calls for heat,"
closing
the R-to-W
circuit.
The fur-
nace control
performs
a self-check,
verifies
the pressure
switch contacts
PRS are open, and starts the inducer motor
IDM.
a. Inducer
Prepurge
Period-
As the inducer
motor
IDM comes up to speed, the pressure
switch contacts
PRS close, 24 VAC power
is supplied
for a field in-
stalled humidifier
at the HUM terminal
and the control
begins
a 15-sec
prepurge
period.
b. Igniter
Warm-Up-
At the end of the prepurge
period,
the Hot-Surface
igniter
HSI is energized
for a
17-second
igniter warm-up
period.
c. Trial-for-Ignition
Sequence-
When the igniter
warm-up
period is completed,
the main gas valve re-
lay contacts
GVR close to energize
the gas valve GV,
the gas valve opens, The gas valve GV permits gas
flow to the burners
where it is ignited
by the HSI. Five
seconds
after the GVR closes, a 2-second
flame prov-
ing period begins.
The HSI igniter will remain
ener-

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pg8jaa

Table of Contents