Sears PG8MAA Installation, Start-Up And Service Instructions Manual page 33

Single-stage deluxe induced-combustion 4-way multipoise gas furnace
Table of Contents

Advertisement

8001-9000
32-38
0.86
(2438-2743)
9001-10,000
38-40
0.82
(2743 -3048)
* Derate multiplier factors are based on midpoint altitude for altitude
range.
FIRE
HAZARD
Failure
to follow
this warning
could
result
in iniury,
death
and/or property
damage.
DO NOT
bottom
out gas valve
regulator
adjusting
screw.
This can result
in unregulated
manifold
pressure
and result
in excess overfire
and heat exchanger
failures.
FURNACE
DAMAGE
HAZARD
Failure
to follow
this caution
may result in reduced
furnace
life.
DO NOT
redrill
orifices.
Improper
drilling
(burrs,
out-of
round
holes,
etc.)
can cause
excessive
burner
noise
and
misdirection
of burner
flames.
This
can result
in flame
impingement
of heat exchangers,
causing
failures.
(See Fig.
43.)
Furnace
gas
input
rate
on rating
plate
is for
installations
at
altitudes
up to 2000
ft. (610 M).
Furnace
input
rate must
be
within +/-2 percent
of furnace
rating plate input.
1. Determine
the correct gas input rate.
The input rating for altitudes
above 2,000 ft. (610 M) must
be reduced
by 4 percent
for each 1,000 ft. (305 M) above
sea level. For installations
below
2000 ft., refer to the unit
rating plate. For installations
above 2000 ft. (610 M), mul-
tiply the input on the rating
plate by the derate multiplier
in Table
10 for the correct
input rate.
2. Determine
the correct
orifice and manifold
pressure
adjust-
ment. There
are two different
orifice and manifold
adjust-
ment tables. All models
in all positions,
except
Low NOx
models
in downflow
or horizontal
positions,
use Table 14
(22,000
Btuh/Burner).
Low NOx models
in the downflow
or horizontal
positions
must use Table 15 (21,000
Btuh/Burner).
See input
listed
on rating
plate.
a. Obtain
average yearly
gas heat value (at installed
alti-
tude) from local gas supplier.
b. Obtain
average yearly
gas specific gravity
from local
gas supplier.
c. Find installation
altitude
in Table 14 or 15.
d. Find closest natural
gas heat value and specific gravity
in Table 14 or 15.
e. Follow
heat value and specific gravity
lines to point of
intersection
to find orifice
size and manifold
pressure
settings
for proper operation.
f. Check and verify burner
orifice size in furnace.
NEVER
ASSUME
ORIFICE
SIZE.
ALWAYS
CHECK
AND VERIFY.
g. Replace
orifice with correct
size if required
by Table
14 or 15. Use only factory-supplied
orifices. See
EXAMPLE
2.
EXAMPLE
2:(0-2000
ft. (0-610
M) altitude)
For 22,000
Btuh per burner
application
use Table 14.
Heating
value = 1000 Btuh/cu
ft.
Specific
gravity = 0.62
Therefore:
Orifice No. 43"
Manifold
pressure:
3.7-In.
W.C.
*Furnace
is shipped
with No. 43 orifices.
In this example
all
main burner
orifices
are the correct size and do not need to be
changed
to obtain proper
input rate.
3. Adjust manifold
pressure
to obtain correct
input rate.
a. Turn gas valve ON/OFF
switch to OFF.
b. Remove
manifold
pressure
tap plug from gas valve.
(See Fig. 42.)
c. Connect
a water column
manometer
or similar
device
to manifold
pressure
tap.
d. Turn gas valve ON/OFF
switch to ON.
e. Manually
close blower
door switch.
f. Set thermostat
to call for heat.
g. Jumper
R and W thermostat
connections
on furnace
control board to start furnace.
h. Remove
regulator
seal cap and turn regulator
adjusting
screw counterclockwise
(out) to decrease
input rate of
clockwise
(in) to increase
input rate.
i. Install regulator
seal cap.
j. Leave manometer
or similar device
connected
and
proceed
to Step 4.
NOTE:
DO NOT set manifold
pressure
less than 3.2-In.
W.C. or
more than 3.8-In.
W.C. for natural
gas at sea level.
If manifold
pressure
is outside
this range, change
main burner orifices
or refer
Table 14 or 15.
NOTE:
If orifice hole appears
damaged
or it is suspected
to have
been
redrilled,
check
orifice
hole with
a numbered
drill bit of
correct
size.
Never
redrill
an orifice.
A burr-free
and squarely
aligned
orifice
hole is essential
for proper flame characteristics.
4. Verify natural
gas input rate by clocking
meter.
NOTE:
Gas valve regulator
adjustment
cap must be in place for
proper input to be clocked.
a. Turn off all other gas appliances
and pilots served by
the meter.
b. Run furnace
for 3 minutes
in heating
operation.
c. Measure
time (in sec) for gas meter to complete
1 re-
volution
and note reading.
The 2 or 5 cubic feet dial
provides
a more accurate
measurement
of gas flow.
d. Refer to Table 12 for cubic ft. of gas per hr.
e. Multiply
gas rate (cu ft./hr) by heating
value (Btu/cu
ft.) to obtain
input.
If clocked
rate
does
not match
required
input
from
Step
1,
increase
manifold
pressure
to increase
input or decrease
manifold
pressure
to decrease
input. Repeat
steps b through
e until correct
input is achieved.
Reinstall
regulator
seal cap on gas valve.
5. Set temperature
rise. The furnace
must operate
within
the
temperature
rise ranges
specified
on the furnace
rating
plate.
Do not exceed
temperature
rise range
specified
on
unit rating
plate.
Determine
the temperature
rise as fol-
lows:
NOTE:
Blower
access
door
must
be installed
when
taking
temperature
rise reading.
Leaving
blower
access
door
off will
result in incorrect
temperature
measurements.
a. Place thermometers
in return and supply
ducts as close
to furnace
as possible.
Be sure thermometers
do not
see radiant
heat from heat exchangers.
Radiant
heat
affects temperature
rise readings.
This practice
is par-
ticularly
important
with straight-run
ducts,
!i
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pg8jaa

Table of Contents