INSTALLATION

FLOOR PROTECTION

A combustible floor must be protected by non-combustible
material (like tile, concrete board, or certified to UL-1618 or
as defined by local codes) extending beneath the heater and
a minimum of 8" (203mm) from each side and minimum 16"
(406mm) from the front face of the stove and minimum 6"
(or the rear clearance to combustibles whichever is smaller)
from the rear of the stove.
When installed with horizontal venting, non-combustible floor
protection must beneath the flue pipe and extend 2" (51mm)
beyond each side.
Minimum Overall Width (X) of Floor
Protector for all installations:
Stove
F3500
12
42" (1067 mm)
Unit
F3500
USA
Canada
The rear clearance to combustibles is less than 6" (for corner installations the rear corners may
be angled to take advantage of the closer clearances.
8
NOTE: USA clearances shown above.
NOTE: In Canada, floor protection must extend 18" (450mm) to the front
and 8" (203mm) to each side and back of the stove.
Minimum Overall Depth (Y) of Floor Protector
Residential
Close Clearance
Y
Z
46-1/2"
8"
48-1/2"
8"
8
8
Mobile Home
Close Clearance
Y
Z
Y
46-1/2
8"
46-1/2
48-1/2"
8"
48-1/2"
F3500 Regency Freestanding Woodstove
8
Alcove
Z
8"
8"