Dry Operation - Mitsubishi Electric MSC-CA20VB Service Technical Manual

Table of Contents

Advertisement

3. Coil frost prevention
Temperature control
When the indoor coil thermistor RT12 reads 4°C or below(MSC-CA20/CA25/CB20/CB25/GA20/GA25VB) / 0°C or
below(MSC-CA35/CB35/GA35VB) for 5 minutes, the coil frost prevention mode starts.
The indoor fan operates at the set speed and the compressor stops for 5 minutes.
After that, if RT12 still reads below 4°C (MSC-CA20/CA25/CB20/CB25/GA20/GA25VB) / 0°C (MSC-CA35/CB35/GA35VB),
this mode is prolonged until RT12 reads over 4°C (MSC-CA20/CA25/CB20/CB25/GA20/GA25VB) / 0°C (MSC-
CA35/CB35/GA35VB).
Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, the compressor stops for 3 minutes.
The indoor fan operates at the set speed.
a. Compressor has been continuously operating.
b. Indoor fan speed is Low or Med.
c. Room temperature is below 26°C.
When compressor stops, the accumulated time is cancelled. When compressor restarts, time counting starts
from the beginning.
Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds
26°C. However, when two of the above conditions (b.and c.) are satisfied again, time accumulation is resumed.
Operation chart
Example
OFF
Compressor
Outdoor fan
ON
Indoor fan
1-2. DRY (
) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select DRY mode with the OPERATION SELECT button.
(3) The microprocessor reads the room temperature and determines the set tem-
perature. Set temperature is as shown on the right chart.
DRY operation will not function when the room temperature is 13°C or below.
(4) When DRY operation functions the fan speed is lower than COOL operation
except at (fan speed) Low.
The system for dry operation uses the same refrigerant circuit as the cooling
circuit.
The compressor and the indoor fan are controlled by the room temperature.
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
Room temperature minus set temperature : 0.3 : or more················································ON
Room temperature minus set temperature : less than -0.3 :············································OFF
2. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In Auto fan speed becomes Low.
3. The operation of the compressor and indoor / outdoor fan
<MU-GA20/GA25/GA35VB, MUH-GA20/GA25/GA35VB, MUX-2A28/2A59/3A60/3A63/2A70/4A73VB>
Compressor operates by room temperature control and time control.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
• When the room temperature is 23°C or over:
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
• When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
ON
( continuously at set speed)
Initial temperature difference
ON
OFF
7
Set temperature and
:
initial room temperature in dry mode
35
30
25
20
15
10
10
15
20
25
Initial room temperature
Difference between room
temperature and set tem-
perature during operation
Thermostat
Set temperature
:
-0.3
30
35
:
:
0.3