(2) Time chart
Air conditioner ON
Positioning
Standard
opening
degree
about 15 minutes
ON
(3) Control data
(a) Reference value of target discharge temperature
(COOL/HEAT :)
Applied model
A
MUZ-CA25VB
50/46
MUZ-CA35VB
57/45
In COOL operation, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super
heat) at the heat exchanger, and when temperature difference have developed, the indoor coil thermistors adjust
LEV opening degree to get approximate 10 degrees lower temperature than the target temperature in the table
above, thus diminishing super heat.
(b) Reference value of LEV standard opening degree
(COOL/ HEAT pulse)
Applied model
01
MUZ-CA25VB
110/80
MUZ-CA35VB
150/90 170/130 180/140 260/200 280/210 280/210
Air conditioner OFF
(thermostat off)
Opening degree is
corrected according
to discharge
temperature.
B
C
D
54/53
60/58
64/63
67/65
57/53
63/59
02
03
04
120/120
130/160
220/190
Commanded
to open
Time
OFF Time
06
05
04
03
E
F
02
01
67/68
67/72
67/69
67/72
05
06
280/200
280/200
53
D
C
B
A(target discharge temperature)
30
50
70
90
Operational frequency of the compressor
F
E
110
130
(Hz)