7-5-6. Wiring Instructions for the Outdoor Unit
CAUTION
Be sure to correctly align inter-unit cables.
Attach the label
Indoor unit
1 2 4
BKW
Use a dedicated A/C circuit for power.
To make connections to the outdoor unit, remove the
inspection panel and tubing panel.
Do not bring the inter-unit cables or power cable into
contact with tubing or service valves.
Use outdoor unit cable fasteners and fasten the inter-
unit cables at the location where the cables are double-
sheathed.
Arrange the wiring so that the inter-unit cables are con-
tained in the inspection panel and tubing panel, as
shown in Fig. 32.
1 2
3
Terminal board
Inter-unit cables
R
ø1.0 (not provided)
Outdoor unit
Terminal board
1
2
3 4
BKW R
Fasten the
cable with cable
fasteners.
Fig. 32
44
1
2
Power:
Single-phase,
240 V
Power switch
(not provided)
Power cable (not provided)
(ø2.0 mm: Less than 15 m)
(ø2.6 mm: Less than 20 m)
(ø3.5 mm: Less than 26 m)
Be sure to perform grounding.
Attach a ground wire to either the
outdoor unit or indoor unit.
If there is a grounding terminal
inside the room, use the grounding
screw inside the indoor unit.
Be sure to apply the provided labels to both
ends of the inter-unit cables to prevent mis-
wiring. The units will not function if the wiring
connections are incorrect.
Ground