1. OPERATING RANGE

Outdoor Unit : CU-5E34NBE
Indoor Unit
: CS-ME7NKE, CS-ME9NKE, CS-ME12NKE
Cooling
Heating
CS-ME18NKE, CS-ME24NKE
Temperature
Indoor Air Intake Temp.
Maximum
Minimum
Maximum
Minimum
32 °C DB / 23 °C WB
19 °C DB / 14 °C WB
27 °C DB
16 °C DB
5
Outdoor Air Intake Temp.
43 °C DB
– 10 °C DB
24 °C DB / 18 °C WB
– DB / – 15 °C WB