Instruction manual swimming pool dryer AP 50 / AP 70

5 Electrical connection

The AP-dehumidifier is provided without power cables. The electrical installation may only be
carried out by trained specialists (electrician). Before the electric connection of the
dehumidifier, the following items must be checked:
Does the mains voltage coincide with the voltage of the appliance?
Adequate fusing supply system?
Has the required residual-current-operated circuitbreaker (r.c.c.b) been installed in case of
swimming baths?
Is the electrical connection provided with a perfect grounding?
Attention!
Before putting the air dryer into operation, the technical data of the appliance should be
compared to the conditions prevailing in the room of installation!
6 Operation
6.1 Putting into operation
Attention!
Before putting the air dryer into operation, the instruction manual should be studied carefully.
Thus, damages by a false or inappropriate operation as well as by inadequate environmental
conditions can be avoided.
For using the air dryer, please proceed as follows:
After having been transported, the air dryer should rest for abt. 15 min. During this period of
time, the oil distributed inside the refrigerating system and frothed during transport will return
into the compressor. We recommend this procedure since it extends the service life of the
compressor.
The cover must be dismantled for the installation of the dehumidifier. The screws to this are
slightly amenable from the outside. In such a way, the cover must be put down cautiously on a
tender subsoil that they do not topple over and it can not come to disadvantages at the
surface.
The electric connection of the dehumidifier must be carried out by qualified specialists.
Mount the condensate hose (helical hose is enclosed) at the drain (on the left side at the
device) and attach the hose with a clamb.
Connect a hygrostat (accessory) to the wedges planned instead (see circuit diagram) so that if
required the device only works. (see hygrostat control)
If the existing humidity is higher than the set value, the air dryer will start to operate.
If the existing humidity is lower than the set value, the air dryer will not start to operate.
6.2 Hygrostat control
The Luftentfeuchter of AP-series are with terminals for an external hygrostat (accessory). The
wedges are marked correspondingly at the terminal block and bridged on delivery of the
dehumidifier. During installation of a hygrostat, the bridge is to be removed. The hygrostat
should be attached in a well amenable place to the wall. It makes that the air dryer cuts in as
soon as the ambient humidity exceeds the preset value. If the humidity value falls below the
set value, the hygrostat will switch off the device.
From serie July 2003
page 4
AERIAL GmbH