Model Name : AS*A14LGC
[Condition]
Ambient
Indoor / Outdoor - Same temperature
temperature
Refrigerant
Standard amount
amount
Piping
5.0m (Height difference 1m)
length
Power
50Hz - 230V
voltage
Operation
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
condition
Measuring
Measure the low pressure with the pressure meter at the service valve.
method
Measure the outdoor unit overall current with the current clamp meter at Power Cable.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Colling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AS*A14LGC
1.2
RH50%
RH60%
1.1
RH70%
1
0.9
0.8
0.7
0.6
16
18
20
In/outdoor ambient temparature [degC]
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*A14LGC
4.8
RH50%
RH60%
4.6
RH70%
4.4
4.2
4
3.8
3.6
3.4
16
18
20
In/outdoor ambient temparature [degC]
[50Hz-230V]
22
24
26
28
30
[50Hz-230V]
22
24
26
28
30
32
32