Mitsubishi MCFH-13NV Service Manual page 34

Floor and ceiling type
Table of Contents

Advertisement

Operation chart
Example
Compressor
Outdoor fan
Indoor fan
—DRY mode of "I FEEL CONTROL"—
The system for dry operation uses the same refrigerant circuit as the cooling circuit.
The compressor and the indoor fan are controlled by the room temperature.
By such controls, indoor air flow amounts will be reduced in order to lower humidity without much room temperature
decrease.
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
However, in AUTO fan operation, fan speed becomes Low.
2. The operation of the compressor and indoor/ outdoor fan
Compressor operates by temperature control and time control.
Set temperature is controlled to fall 2°C from initial room temperature.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
• When the room temperature is 23°C or over:
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
• When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
Operation time chart
Example
OFF
Thermostat
Indoor fan
OFF
Outdoor fan
OFF
Compressor
3. Coil frost prevention
• The operation is as same as coil frost prevention during COOL mode of "I FEEL CONTROL".
• Indoor fan operates at the set speed and the compressor stops for 5 minutes, because protection (Coil frost
prevention) has the priority.
However, when coil frost prevention works while the compressor is not operating, it's speed becomes Low.
ON
OFF
(continuously at set speed)
ON
ON
ON
OFF
ON
OFF
8 min.
3 min.
OFF
OFF
ON
ON
OFF
ON
ON
OFF
4 min.
1 min.
34
ON
ON