Outdoor Unit - Toshiba RAS-30NKP2B-1 Service Manual

Table of Contents

Advertisement

10-2. Outdoor Unit

No.
Part name
Common
1
procedure
2
Running
capacitor
for compressor
3
Running
capacitor
for fan motor
4
Magnetic
contactor
Spark killer
5
(Cooling only model)
Procedures
1) Stop the operation of the air conditioner and turn off
its main power supply or remove the power supply
cord.
2) Remove the electrical parts cover.
(4 screws ∅4 x 10L)
3) Remove 2 cord clamps (4 screws ∅4 x 22L) and
disconnect the power supply cord and connecting
cable after removing 6 screwson on the terminal
block and 1 ground screw on the electrical parts
base.
4) Remove the top cabinet. (7 screws ∅4 x 10L)
5) Remove the front cabinet. (2 screws ∅4 x 10L)
6) Remove the side cabinet
(4 screws ∅4 x 10L & 2 screws ∅4 x 14L)
1) Perform the common procedure
2) Remove the capacitor band. (1 screw ∅ 4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor
terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws ∅4 x 10L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the terminal.
1
Spark killer
Magnetic contactor
– 54 –
FILE NO. SVM-06017
Remarks
Top cabinet
Electrical
parts cover
Front cabinet
Side cabinet
4 screws ∅4 x 22L
Running capacitor
for compressor
Running capacitor
for fan motor

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ras-30n2a2bRas-30n2a-arRas-30nkp-ar-1

Table of Contents