Outdoor Unit Installation; Minimum Clearance; Outdoor Installation Precaution; Drain Elbow Installation - Carrier 42HQE009 Installation Manual

Hide thumbs Also See for 42HQE009:
Table of Contents

Advertisement

42HQE009/012/018/022-38YE009/012/018/022

Outdoor unit installation

Minimum clearances (mm)
B

Outdoor installation precaution

• Install the outdoor unit on a rigid base to prevent increasing noise
level and vibration.
• Determine the air outlet direction where the discharged air is no
blocked.
• In the case that the installation place is exposed to strong wind
such as a seaside operation by putting the unit lengthwise along
the wall or using a dust or shield plates.
• Specially in windy area, install the unit to prevent the admission of
wind. The connection between bracket and wall, bracket and the
air conditioner should be firm, stable and reliable.
• If need suspending installation, the installation bracket should
accord with technique requirement in the installation bracket
diagram.
A
C
A
F
Strong wind
Mod.
38YE009/012
A mm
100 mm or more
B mm
100 mm or more
C mm
600 mm or more
D mm
100 mm or more
E mm
1000 mm or more
F mm
600 mm or more

Drain elbow installation

Fit the seal into the drain elbow, then insert the drain elbow
into the base pan hole of outdoor unit, rotate 90 to securely
assemble them. Connecting the drain elbow with an extension
drain hose (Locally purchased), in case of the water draining off
the outdoor unit during the heating mode.
E N G L I S H
D
E
38YE018/022
100 mm or more
100 mm or more
600 mm or more
100 mm or more
1000 mm or more
600 mm or more
Base pan hole
of outdoor unit
Seal
Drain elbow
GB - 7