Comfortable Timer Setting; Outline Of Heating Operation - Mitsubishi SRK10CES Technical Handbook

Table of Contents

Advertisement

(6) Comfortable timer setting

If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode operation
is selected, the comfortable timer starts and determines the starting time of next operation based on the initial value of 15 minutes and the
relationship between the room temperature at the setting time (temperature of room temperature sensor) and the setting temperature.
(Max. 60 minutes)
Operation mode
3 < Room temp. – Setting temp.
At cooling
3 < Setting temp. – Room temp.
At heating
Notes (1) At 5 minutes before the timer ON time, operation starts regardless of the temperature of the room temperature sensor (Th1).
(2) This function does not operate when in the Dry or Auto Dry mode.
However, the operation in item (1) does operate in the Auto Dry mode.
(3) During the comfortable timer operation, both the RUN light and TIMER light illuminate and the TIMER light goes off after expiration of the timer, ON setting
time.
(Example) Heating
Setting temperature
Room temperature

(7) Outline of heating operation

(a) Operation of major functional components in heating mode
Functional
components
Indoor fan motor
Flaps
Display
52C
Outdoor fan motor
4-way valve
Electronic expansion valve
Solenoid valve
(b) Air flow selection
(i)
Speed of inverter changes within the range of selected air flow.
Air flow selection
Inverter command speed
Auto
Air flow
Inverter command speed
HI
Air flow
Inverter command speed
MED
Air flow
Inverter command speed
LO
Air flow
(ii) When the defrosting, protection device, etc. is actuated, operation is performed in the corresponding mode.
(iii) Outdoor unit blower operates in accordance with the inverter command speed.
+5
+5
Operation starting time
Time
15 min.
10 min.
earlier
earlier
Item
When the inverter
speed is 0rps
ON
ON or OFF
Lights up
ON
OFF
Depending on the stop mode
OFF
Model
Operation start time correction value (Min.)
1 < Room temp. – Setting temp. ≤ 3
No change
2 < Setting temp. – Room temp. ≤ 3
No change
Corrects the starting time of next operation by
calculating the temperature difference.
5 min.
Setting time
earlier
When the inverter speed
is other than 0rps
ON
ON or OFF
Lights up
ON
ON
ON
Depending on the EEV control
OFF
SRK13ZEV-S
12~118rps
Depends on inverter command speed.
12~118rps
Depends on inverter command speed.
12~78rps
Depends on inverter command speed.
12~38rps
4th speed fixed
12
-
-
Room temp. – Setting temp. ≤ 1
=
–5
Setting temp. – Room temp. ≤ 2
=
–5
¡ If the difference (= Setting temperature – Room tempera-
ture) is 4ºC, the correction value is found to be +5 min-
utes from the table shown above so that the starting time
of next operation is determined as follows:
15 min. earlier + 5 min. = 20 min. earlier
Current operation
Correction value
start time
When the inverter speed is 0rps
due to an anomalous stop
OFF
Stop position control
Lights up or flashes
OFF after stop mode
OFF
Depending on the stop mode
OFF
=
=