93/68/EEC (CE mark) Standard to which Conformity is declared: EN61010-1:2001 (Safety requirements for electrical equipment for measurement, control and laboratory use - Part 1) KEPCO INC. Manufacturer's Name and Address: 131-38 SANFORD AVENUE FLUSHING, N.Y. 11352 USA Importer's Name and Address:...
Page 4
There are no user or operator serviceable parts within the product enclosure. Refer all servicing to qualified and trained Kepco service technicians. 228-1351 COND/CONFORM 073008...
SAFETY INSTRUCTIONS 1. Installation, Operation and Service Precautions This product is designed for use in accordance with EN 61010-1 and UL 3101 for Installation Category 2, Pollution Degree 2. Hazardous voltages are present within this product during normal operation. The prod- uct should never be operated with the cover removed unless equivalent protection of the operator from accidental contact with hazardous internal voltages is provided: There are no operator serviceable parts or adjustments within the product enclosure.
TABLE OF CONTENTS SECTION PAGE SECTION 1 - INTRODUCTION Scope of Manual............................1-1 General Description ............................ 1-1 Specifications.............................. 1-1 Features..............................1-8 1.4.1 Local Control ............................1-8 1.4.2 Remote Control ............................1-8 1.4.2.1 Digital Programming........................... 1-8 1.4.2.2 Analog Programming ......................... 1-8 1.4.3 Digital Calibration ............................
Page 8
TABLE OF CONTENTS SECTION PAGE 3.2.6 Setting voltage or current........................3-5 3.2.6.1 Real-time Voltage/Current Adjustment ....................3-6 3.2.6.2 Setpoint Adjustment .......................... 3-6 3.2.6.3 Last Setting Recall..........................3-6 3.2.7 Viewing/Changing Overvoltage or Overcurrent Protection Values ............3-6 3.2.8 Changing GPIB Address......................... 3-7 3.2.9 Changing RS232 Baud Rate ........................
Page 9
TABLE OF CONTENTS SECTION PAGE 3.6.4.5 Data Separator........................... 3-23 3.6.4.6 Message Unit Separator ........................3-23 3.6.4.7 Root Specifier............................. 3-23 3.6.4.8 Message Terminator .......................... 3-24 3.6.5 Understanding The Command Structure....................3-24 3.6.6 Program Message Syntax Summary....................... 3-26 3.6.7 Status Reporting............................3-26 3.6.7.1 Status Reporting Structure.........................
Page 12
PAGE KLP Series Power Supply ........................... viii KLP Operating Regions..........................1-2 KLP Series Power Supply, Mechanical Outline Drawing ................1-6 KLP Series, Front Panel Controls and Indicators..................2-1 KLP Series, Rear Panel Switch and Connectors ..................2-2 Remote Sensing............................2-10 Series Connection using Remote Sensing....................
Page 13
LIST OF TABLES TABLE TITLE PAGE Model Parameters ............................1-2 KLP Specifications ............................1-3 Equipment Supplied ............................1-10 Accessories ..............................1-11 Safety Symbols ............................1-11 Controls, and Indicators ..........................2-1 Analog I/O Switch Functions ........................2-3 IEEE 488 Port Connector (J4) Pin Assignments ..................2-3 RS232 Port Connector (J3) Pin Assignments .....................2-4 Rear Terminal block Assignments ......................2-4 Analog I/O Connector (J2) Pin Assignments ....................2-4 Input Current Service Rating and Conductor Sizes ..................2-7...
Page 14
FIGURE 1-1. KLP SERIES POWER SUPPLY viii KLP073008...
SECTION 1 - INTRODUCTION SCOPE OF MANUAL This manual contains instructions for the installation, operation and service of the KLP series of 1200W output power, stabilized voltage or current, d-c power supplies manufactured by KEPCO, Inc., Flushing, New York, U.S.A.
FIGURE 1-2. KLP OPERATING REGIONS TABLE 1-1. MODEL PARAMETERS Rated Maximum Minimum Rated Maximum Ripple and noise Efficiency Model number Voltage current for programmable Current voltage for @115 Va-c current Range Range rated voltage rated current KLP 20-120-1200 0-20V 60A@20V 1.6A 0-120A 10V@120A...
TABLE 1-2. KLP SPECIFICATIONS SPECIFICATION RATING/DESCRIPTION CONDITION INPUT CHARACTERISTICS nominal 110-240 Va-c Single Phase a-c voltage range 100-255 Va-c Wide Range; contact factory for opera- tion to 265V a-c. d-c voltage range 125-420 Vd-c No regulatory agency approval nominal range 50-60 Hz Frequency maximum...
TABLE 1-2. KLP SPECIFICATIONS (Continued) SPECIFICATION RATING/DESCRIPTION CONDITION GENERAL (ENVIRONMENTAL) SPECIFICATIONS Temperature operating -20 to +50 deg C Rated load. Derate at 25W per °C between 50 and 70°C. storage -40 to +85 deg C Cooling 3 internal d-c fans exhaust to the rear Humidity 0 to 95% RH...
Page 19
TABLE 1-2. KLP SPECIFICATIONS (Continued) SPECIFICATION RATING/DESCRIPTION CONDITION PROGRAMMING CHARACTERISTICS - ANALOG Analog remote control selection Activate with jumper at analog program- Recognized during power up. ming connector isolation Safety Extra Low Voltage (SELV) referenced to chassis Programming by voltage voltage 0-10V Programmable current minimal value-10V...
FEATURES 1.4.1 LOCAL CONTROL Two front panel rotary encoders allow setting of voltage and current setpoints and limits. Oper- ating mode of the power supply is indicated by lighting either a green (Constant Voltage) or amber (Constant Current) LED. The output can be enabled or disabled by the front panel DC OUTPUT switch;...
1.4.9 BUILT-IN PROTECTION KLP Series Power Supplies provide built-in protection against the conditions listed below. In each case, a detected fault results in immediate latched shutdown of the power supply output. In addition, the status display flashes the appropriate indication and the status bit is set for retrieval through either of the digital programming ports.
There are no operator serviceable parts inside the case. Service must be referred to authorized personnel. Using the power supply in a manner not specified by Kepco. Inc. may impair the pro- tection provided by the power supply. Observe all safety precautions noted throughout this man- ual.
Mates with NEMA 5-15R receptacle (see adjacent figure). Supports restricted load power over mains voltage range of 90-136V a-c (contact Kepco Sales Engineering for details). Line Cord Set (250V/15A) 2.5m long cord set, provides for source power NEMA 6-15R 118-1137 connection.
FRONT PANEL CONTROLS AND INDICATORS. Refer to Figure 2-1 and Table 2-1. 2.2.2 REAR PANEL CONNECTORS AND SWITCH. Refer to Figure 2-2 and Tables 2-2 through 2- FIGURE 2-1. KLP SERIES, FRONT PANEL CONTROLS AND INDICATORS TABLE 2-1. CONTROLS, AND INDICATORS FIGURE 2-1 CONTROL OR FUNCTION INDEX NO.
RS232 baud rate (PAR. 3.2.9) and (for -1200 models) set user-determined limits on voltage and current (virtual model) (PAR. 3.2.5). NOTE: Requires a thin tool (e.g., end of paper clip) to press switch. FIGURE 2-2. KLP SERIES, REAR PANEL SWITCH AND CONNECTORS KLP-HV 073008...
TABLE 2-2. ANALOG I/O SWITCH FUNCTIONS DIP SWITCH FUNCTION SETTINGS POSITION Allows analog programming commands for voltage to be provided Selects Resistance by either variable voltage (PAR. 3.7.3) or resistance (PAR. 3.7.2). OFF: Selects Voltage (factory When resistance mode is selected, an internal 1mA current genera- default) tor provides the reference for voltage programming.
TABLE 2-4. RS232 PORT CONNECTOR (J3) PIN ASSIGNMENTS CONNECTOR SIGNAL NAME FUNCTION NOTE: A null modem cable (see Table 1-4) is required for nearly all applications, with the exception of those in which RXD and TXD line transposition is accomplished via external hardware (e.g. older Apple MAC computers with D-sub serial port). SGND Signal Ground Receive Data...
SOURCE POWER REQUIREMENTS This power supply operates with the installed circuit breaker from either d-c or single phase a-c mains power over the voltage and frequency ranges specified in Table 1-2 without adjustment or modification. COOLING The power devices used within the power supply are maintained within their operating tempera- ture range by means of internal heat sink assemblies cooled by three internal (d-c type) cooling fans.
• Then the status display reads SET (setpoint mode), the DC VOLTS display reads 0000 Volts, the DC AMPERES display reads minimum Amperes (see Note 1, below). NOTES: 1. A minimum programmed current (actual value depends on model) is required to ensure proper operation of the power supply under all load conditions.
It is the user's responsibility to ensure that all applicable local codes for source power wiring are met. Kepco also makes a variety of prefabricated safety line cord sets available for connecting KLP to source power via conven- tional box-mounted receptacles.
For other options please contact Kepco Sales Engineering with specific requirements. WARNING IT IS IMPERATIVE THAT THE USER PROVIDE ALL THREE SOURCE WIRE CONNEC- TIONS, AS THIS CONNECTION IS THE SAFETY GROUND PROVISION! 2.7.3 D-C OUTPUT GROUNDING Connections between the power supply and the load and sensing connections may, despite precautions such as shielding, twisting of wire pairs, etc., be influenced by radiated noise, or...
2.7.4 POWER SUPPLY/LOAD INTERFACE The general function of a voltage or current stabilized power supply is to deliver the rated output quantities to the connected load. The load may have any conceivable characteristic: it may be fixed or variable, it may have predominantly resistive, capacitive or inductive parameters; it may be located very close to the power supply output terminals or it may be a considerable distance away.
The user must also respect the ±600V d-c maximum isolation from output to chassis when determining the maximum series voltage. Figure 2-4 shows a series connection of two KLP power supplies using remote sensing. Kepco strongly recommends that series applica- tions employ master/slave control as described in PAR’s. 2.7.8 and 3.2.10.
2.7.7.1 LOAD SHARING When operating two or more power supplies in parallel, either for capacity or redundancy, it is desirable to distribute the load equally among all of the power supplies in order to improve per- formance, reduce stress and increase reliability. KLP power supplies incorporate active circuitry which forces multiple power supplies wired in parallel to share load current, both in voltage- and current-mode regulation.
These signals must be protected from radiated and conducted noise as well as from physical contact with non-valid driving sources. The following subsections address specific programming signal applications; in general, however, when accessing this connector from distant locations or high-noise environments, it is recommended that a shielded cable be used, with the shield terminated to the system's single point ground.
SECTION 3 - OPERATION GENERAL This section explains how to operate the KLP Power Supply. Series KLP feature three modes of operation: • Local Mode: This is the default operating mode, providing full access to all programming and readback functions via front panel displays, controls, and indicators (see PAR. 3.2). •...
• output is disabled (green DC OUTPUT indicator is off). If remote analog mode is selected (PAR. 3.7), output is enabled unless Remote Inhibit, pin 8 of the Analog I/O Connector (see Figure 2-2 and Table 2-6) is grounded. • DC VOLTS and DC AMPERES displays show programmed output conditions: either 0 Volts, minimum Amperes (see NOTE, PAR.
NOTE: During both LOCAL and DIGITAL REMOTE operation, the analog readback signals (voltage and current) remain available, as does the remote inhibit signal; only program- ming signals are disregarded. ANALOG REMOTE: With power supply turned off, ground Analog I/O port pin 12. Refer to PAR. 2.7.9 to configure the Analog I/O Port;...
3.2.4 CHECKING VOLTAGE/CURRENT SETPOINTS CAUTION: WHEN THE OUTPUT IS DISABLED, THE DC VOLTS AND DC AMPERES DIS- PLAYS SHOW THE ACTUAL OUTPUT VOLTAGE AND CURRENT. BEFORE ENABLING THE OUTPUT ALWAYS CHECK THE SETPOINTS TO AVOID POS- SIBLE DAMAGE TO THE LOAD. Check the voltage and current set points by tapping either the VOLTAGE or CURRENT control.
To define a virtual model, proceed as follows. (To establish a virtual model using SCPI com- mands, use VOLT:LIM:HIGH (see PAR. B.49) and CURR:LIM:HIGH (see PAR. B.37), respec- tively.) 1. If the status display shows SET, tap either the CURRENT or VOLTAGE controls to take the unit out of setpoint mode (status display goes from SET to blank) 2.
3.2.6.1 REAL-TIME VOLTAGE/CURRENT ADJUSTMENT Rotating the associated control will change the output voltage or current in real-time only if the output is enabled. If the unit is in constant voltage mode (CV indicator lit) the DC VOLTS display shows the actual output voltage as the VOLTAGE control is rotated. Similarly, if the unit is in constant current mode (CC indicator lit) the DC AMPERES display shows the actual output cur- rent as the CURRENT control is rotated.
age/current exceeds the overvoltage/overcurrent protection value, the protection circuit latches the output off, flashes an overvoltage (OVP) or overcurrent (OCP) error message on the status display and sets a status bit that can be retrieved through the RS 232 or GPIB port. The unit must be cycled on and off to restore the output.
2. Using a thin tool (e.g., a paper clip), press the FUNCTION switch repeatedly until the status display reads BAUD; the active baud rate is visible in the DC AMPERES display (value shown must be multiplied by 1000; e.g., 9600 is displayed as 9.6). To change the baud rate, proceed to step 2, otherwise, press FUNCTION to exit.
3.2.10.2 CONFIGURE POWER SUPPLY AS SLAVE 1. Turn power on. If the unit comes up in setpoint mode (see PAR. 3.2.4), tap either the CUR- RENT or VOLTAGE control to take the unit out of setpoint mode (status display goes from SET to blank).
• If analog control is used, only the master is configured for analog control (the slave is controlled digitally by the master). • If Remote Inhibit is used, it should only be connected to the master. • If E241 (hardware error) is showing in the status display, the FUNCTION switch can be used to change the configuration •...
3.2.11.2 DISPLAY MODEL Enter UTIL menu and rotate either VOLTAGE or CURRENT control until status display reads MODL (see PAR. 3.2.11). • The DC VOLTS display shows the model voltage rating (e.g, 75 for KLP 75-33-1200). • The DC AMPS display shows the model current rating (e.g, 33 for KLP 75-33-1200). 3.2.11.3 RELAY CONTROL Enter UTIL menu and rotate either VOLTAGE or CURRENT control until status display reads...
NOTE: Once the relay turns on in V->C or C->V mode, the relay will go off again when the unit transitions back to the original mode, or when the output is turned off. 4. When the relay control mode is set to MAN, the DC VOLTS display shows whether the relay is ON or OFF.
• The DC VOLTS display shows the month and day of the active calibration date. • The DC AMPS display shows the year of the active calibration date. Tap the DC OUTPUT switch to proceed to the system calibration (see PAR 4.3). DIGITAL REMOTE MODE PROGRAMMING USING SCPI COMMANDS KLP Power Supplies may be programmed over a control bus using SCPI (Standard Commands for Programmable Instruments).
Each location defines values for the active channel (either output voltage or output current), a dwell time duration (between 0.010 and 655.36 seconds) for the programmed settings, and the state of the internal relay. By programming the output to change in small increments, complex outputs can be generated.
• ON (enabled) NOTE: Kepco strongly recommends the XON XOFF method for data transfer via RS 232 protocol for all Kepco products. If this method is not selected, it is the user's responsibility to ensure completion of any response by the power supply prior to issuance of subsequent commands.
XOFF) the host controller can ensure that serial data interrupts occurring after parsing of the incoming message do not result in lost data. Figure 3-1 illustrates the default echo mode, the prompt method and the XON XOFF method described in the following paragraphs. Only four control characters (characters between 00 and 1F ) are acknowledged by the power...
If each of the above steps is completed successfully, the problem lies in the computer hard- ware and/or software. Refer to the Product Support area of the Kepco website for additional information regarding RS 232 Communications problems: www.kepcopower.com/support. IEEE 488 (GPIB) BUS PROTOCOL...
tener). Tables 3-3 and 3-4 define the messages sent to the KLP, or received by the KLP, via the IEEE 488 bus in IEEE 488 command mode and IEEE 488 data mode, respectively. These mes- sages are enabled during the “handshake” cycle, with the KLP power supply operating as either a Talker or a Listener.
Download the latest VISA driver from the Kepco website at http://www.kepcopower.com/drivers.htm Although the software drivers supplied by Kepco are VISA compliant, they also require the installation of the proper 16-bit VISA driver from your GPIB card supplier. Many vendors supply this software with the hardware;...
3.6.1 SCPI MESSAGES There are two kinds of SCPI messages: program messages from controller to power supply, and response messages from the power supply to the controller. Program messages consist of one or more properly formatted commands/queries and instruct the power supply to perform an action;...
3.6.3.10 CALIBRATE SUBSYSTEM The KLP series of power supplies support software calibration. A full calibration consists of a voltage calibration and a current calibration. Both voltage and current calibrations consist of a zero and a full scale calibration. There are two ways to perform the calibration: locally using the front panel keys, or remotely sending commands through the GPIB bus.
rated by a space; the parameter is usually numeric (e.g., CURR 5<newline>), but may also be a string (e.g., OUTP ON<newline>). Figure 3-2 illustrates the message structure, showing how message units are combined. The following subparagraphs explain each component of the message structure.
3.6.4.4 DATA Some commands require data to accompany the keyword either in the form of a numeric value or character string. Data always follows the last keyword of a command or query (e.g., VOLT:LEV:TRIG 14 or SOUR:VOLT? MAX 3.6.4.5 DATA SEPARATOR Data must be separated from the last keyword by a space (e.g., VOLT:LEV:TRIG 14 or SOUR:VOLT? MAX KEYWORD...
• new line (<NL>), ASCII 10 (decimal) or 0A (hex) NOTE: Kepco power supplies require a message terminator at the end of each program mes- sage. The examples shown in this manual assume a message terminator will be added at the end of each message. Where a message terminator is shown it is represented as <NL>...
ROOT : (colon) SYSTem subsystem STATus subsystem ABORt subsystem [SOURce:] subsystem SYSTem STATus ABORt [SOURce:] :OPERation :COMM VOLTage :GPIB:ADDR val :CONDition? CALibrate subsystem [:LEVel] :GPIB:ADDR? :ENABle val [:IMMediate] CALibrate :SER:BAUD val :ENABle? [:AMPLitude] val :CEXTernal :SER:BAUD? [:EVENt]? [:AMPLitude]? MIN, MAX :CGAin (0 | 1) :PRESet...
3.6.6 PROGRAM MESSAGE SYNTAX SUMMARY • Common commands begin with an asterisk (*). • Queries end with a question mark (?). • Program messages consist of a root keyword and, in some cases, one or more mes- sage units separated by a colon (:) followed by a message terminator. Several mes- sage units of a program message may be separated by a semicolon (;) without repeating the root keyword.
A zero to one transition of a condition register is added to the event register if the specific bit in the enable register is also a 1. Reading an event register clears all of the bits found in the event register.
3.6.7.2 OPERATIONAL STATUS REGISTER The OPERational condition register contains conditions which are a part of the instrument’s nor- mal operation. The definition of each of these bits (condition register) is as follows: • 1 through 4 - Not Used — always zero. •...
Enabling and disabling the output is accomplished via the analog I/O port using pin 8. Logic 0 (ground) turns the output off, Logic 1 (open) turns the output on. /**************************************************************************/ Sample Program For KEPCO power supply, using National Instruments GPIB interface card and IBM PC or compatible computer /**************************************************************************/ #include <stdio.h>...
3.7.2 PROGRAMMING WITH EXTERNAL RESISTANCE Figure 3-6 is a simplified diagrams of the KLP showing the switch configuration and external connections required for analog programming using an external resistance. 1. Overvoltage and Overcurrent settings must be established via either local programming or digital remote programming prior to initiating Analog Remote programming.
3.7.3 PROGRAMMING WITH EXTERNAL VOLTAGE Figure 3-7 is a simplified diagrams of the KLP showing the switch configuration and external connections required for analog programming using an external voltage. 1. Virtual Model (PAR. 3.2.5) and Overvoltage and Overcurrent settings (PAR. 3.7.4) must be established via either local programming or digital remote programming prior to initiating Analog Remote programming.
Page 72
PROGRAMMING MODE Overvoltage and overcurrent values can not be changed using analog remote programming; this can only be done by issuing a command via the GPIB or RS232 port, or via local mode from the front panel (enter local mode by pressing the VOLTAGE and CURRENT adjustment con- trols at the same time).
SECTION 4 - CALIBRATION GENERAL This section contains the calibration instructions for the Power Supply. It is recommended that the user be familiar with Local Mode operation (PAR.3.2) before calibrating the unit. A full calibration consist of a voltage calibration and a current calibration. Both voltage and cur- rent calibrations consist of a zero and a full scale calibration.
will be connected across the output terminals and the digital voltmeter will be connected across the sense terminals of the shunt resistor. 1. Turn off power supply and disconnect load from output terminals at the rear of the unit. 2. Verify that power supply is configured for local error sensing (PAR. 2.7.5.1). 3.
3. Tap the DC OUTPUT switch to accept the value. The status display then reads OUTV. Con- nect the DVM to ANALOG I/O PORT J2, pin 13 (M–) and pin 6 (M+). Rotate the VOLTAGE control to increase or decrease the output voltage until the DVM reads as close as possible to 10V.
1. The status display reads INPV. Refer to PAR 3.7 to connect the reference voltage used to define full scale output voltage. as the source as described in PAR 3.7. 2. When the reference voltage is at the desired value, tap the DC OUTPUT switch to accept the value.
1. Turn off power supply and disconnect load from output bus bar at the rear of the unit. 2. Verify that power supply is configured for local error sensing (See PAR. 2.7.5.1). 3. For voltage calibration connect DVM to (M+, S+) and (M–, S–) of terminal block at the rear of power supply.
4.4.2 CURRENT CALIBRATION (VISA DEMO) During current calibration, the current, current readback and analog current readback are cali- brated. 1. Click the CURRENT button on the Calibration window to start Current calibration; the status display (on the main panel) reads LOAD. When the shunt and DVM are connected per PAR. 4.4, step 4, click the CURRENT button to start current calibration.
3. The status display reads INPC. Connect the reference voltage used to define full scale out- put current as described in PAR 3.7. 4. When the reference voltage is at the desired value, click the PRESS TO ACCEPT button to accept the value.
Working. Each time the unit is calibrated, the Working values are moved to Previous, and the new calibration values are stored in Working. It is possible to replace the Working calibration values with either the Previous or the Factory calibration values; contact Kepco Sales Engineer- ing for details.
APPENDIX A - IEEE 488.2 COMMAND/QUERY DEFINITIONS INTRODUCTION This appendix defines the IEEE 488.2 commands and queries used with the KLP Power Supply These commands and queries are preceded by an asterisk (*) and are defined and explained in Fig- ures A-1 through A-14, arranged in alphabetical order.
The character string contains the following fields: <Manufacturer>, <Model>, <Manufacturing Data>, <Firmware revision> where: <Manufacturer> = KEPCO, <Model> = KLP V V- CC-1200 (V V is Eo CC is Io ,) <Manufacturing Data>=DDMMYYYY-NNNNNN (DD=day, MM=month, and YYYY=year...
Returns 32 (bit 5 set), indicating command error has occurred since the last time the register was read. *IDN? Returns: "KEPCO, KLP 75-33-1200, mm-dd-yyyy, Axxxxxx, Vx.xx" where mm-dd-yyyy indicates date of last calibration, Axxxxxx indicates unit serial number and Vx.xx indicates firmware revision.
*RCL *RCL — RECALL COMMAND Syntax: *RCL <integer> (1 to 40) Description: Restores power supply to previously defined levels of output voltage, output current, overvolt- age protection, overcurrent protection, output state (on or off) and relay state. Executing *RCL recalls the settings previously saved by *SAV from one of 40 memory locations, changing the voltage, current, overvoltage protection, overcurrent protection, and output on/off state accordingly.
*SRE? A.13 *SRE? — SERVICE REQUEST ENABLE QUERY Syntax: *SRE? Response: <integer> = value from 0 - 255 per Table A-3. Description: Reads the Service Enable Register. Used to determine which events of the Status Byte Register are programmed to cause the power supply to generate a service request (1 = set = function enabled, 0 = reset = function disabled).
APPENDIX B - SCPI COMMAND/QUERY DEFINITIONS INTRODUCTION This appendix defines the SCPI subsystem commands and queries used with the KLP Power Supply. Subsystem commands are defined in PAR. B.3 through B.92, arranged Alphabetically in groups as they appear in the tree diagram, Figure 3-3. Table B-1 provides a quick reference of all SCPI subsystem commands and queries used in the Interface Card.
To use these commands, refer to Kepco’s website (www.kepcopower.com/drivers) and download the LabWindows/ CVI Version 5 driver for KLP. This file provides remote calibration capability and uses the following...
NOTE: The following example assumes KLP 75-33-1200 with virtual model set for 75V, 16A and output operating in voltage stabilization mode. See Figure B-3 for directions on programming virtual model limits. OUTP ON Enables output. OUTP? Returns 1 (output enabled). VOLT 75;CURR 1.5E-1 Programs output voltage to 75V, current limit to 0.15A.
LIST:CONT B.10 [SOURce:]LIST:CONTrol COMMAND Syntax: Short Form: LIST:CONT<boolean> Long Form: LIST:CONTrol><boolean> where boolean = 0 or OFF, 1 or ON Description: If relay control set to LIST, allows user to energize (1 or ON) or de-energize (0 or OFF) internal relay using LIST commands.
LIST:CURR? B.17 [SOURce:]LIST:CURRent? QUERY Syntax: Short Form: LIST:CURR? Long Form: LIST:CURRent? Return Value: <value1>, <value2>, . . . to <value16> Description: Identifies the parameters (main channel) entered for the list. Starting at location established by LIST:QUERy, returns comma-separated list of up to 16 values indicating the main channel parameters entered.
LIST:QUER B.24 [SOURce:]LIST:QUERY COMMAND Syntax: Short Form: LIST:QUER <int_value> Long Form: LIST:QUERy <int_value> int_value = 0 to 1001 Description: Determines first location to be queried by LIST:SEQ? query. Related Commands: LIST:SEQ?. LIST:QUER?. (See example, Figure B-2.) LIST:QUER? B.25 [SOURce:]LIST:QUERY? QUERY Syntax: Short Form: LIST:SEQ? Long Form: LIST:SEQuence?
NOTE: The following example assumes KLP 75-33-1200 with virtual model set for 36V, 33.33A and out- put operating in voltage stabilization mode. See Figure B-3 for directions on programming virtual model limits. LIST:CLE Clears main channel (LIST:CURR or LIST:VOLT) and LIST:DWEL data tables and initializes the LIST processor to add entries.
OUTP B.31 OUTPut[:STATe] COMMAND Syntax: Short Form: OUTP[:STAT] <boolean> Long Form: OUTPut[:STATe] <boolean> <boolean>=(0 or OFF, 1 or ON) Description: Enables or disables the power supply output (see PAR.3.7.1 for disabling if analog program- ming used). Upon power up the output is enabled (OUTP ON). When OUTP OFF is executed, the digitally programmed values of voltage and current are saved, then voltage and current are pro- grammed to 0;...
Description: Identifies active voltage mode. Returns LIST while list is being executed. TRAN (transient) is not supported at this time, contact Kepco for more information. Returns FIXED while in fixed (default) mode of operation. Related Commands: LIST commands. (See example, Figure B-2.)
NOTE: The following example assumes KLP 75-33-1200 with virtual model set for 75V, 16A. SYST:PASS:CEN 7533 Enables access to the protected commands. NOTE: Password shown is factory default value for KLP 75-33-1200; values will vary for other models (see Table 4-1) and can be altered by user. VOLT:LIM:HIGH? Returns 7.5E1 (75V, virtual model voltage rating).
NOTE: The following example assumes KLP 75-33-1200 with virtual model set for 36V, 33.33A and output operating in current stabilization mode. See Figure B-3 for directions on programming virtual model limits. VOLT 32.1;CURR 4 Programs output voltage for 32.1V, output current for 4A. OUTP ON Enables output.
FUNC:MODE? B.46 [SOURce:]FUNCtion:MODE? QUERY Syntax: Short Form: FUNC:MODE? Long Form: [SOURce:]FUNCtion:MODE? Return Value: String1,String2 where string 1is the actual operating mode: VOLT = Constant Voltage mode (CV).CURR = Constant Current mode (CC) and string 2 is the mode that was commanded using FUNC:MODE.
Description: Identifies active voltage mode. Returns LIST while list is being executed. TRAN (transient) is not supported at this time, contact Kepco for more information. Returns FIXED while in fixed (default) mode of operation. Related Commands: LIST commands. (See example, Figure B-2.) VOLT:PROT B.53 [SOURce:]VOLTage:PROTection[:LEVel] COMMAND...
NOTE: The following example assumes KLP 75-33-1200 with virtual model set for 36V, 33.33A and output operating in voltage stabilization mode. See Figure B-3 for directions on programming virtual model limits. VOLT 21.8;CURR .5 Programs output voltage for 21.8V, output current for 0.5A. OUTP ON Enables output.
STAT:OPER:ENAB B.58 STATus:OPERation:ENABle COMMAND Syntax: Short Form: STAT:OPER:ENAB <int_value> 0 to 1313 (1 + 32 + 256 + 1024) Long Form: STATus:OPERation:ENABle <int_value> 0 to 1313 (1 + 32 + 256 + 1024) Description: Sets Operation Enable Register. The Operation Enable Register is a mask for enabling specific bits in the Operation Event Register which will cause the operation summary bit (bit 7) of the Status Byte register to be set Bit set to 1 = function enabled (active, true);...
STAT:PRES B.61 STATus:PRESet COMMAND Syntax: Short Form: STAT:PRES Long Form: STATus:PRESet Description: Disables reporting of all status events. This command sets all bits of the Operation Condition (Table B-2) and Questionable Condition Registers to 0, preventing all status events from being reported.
= function enabled (active, true); bit reset to 0 = function disabled (inactive, false) Related Com- mands: STAT:QUES?. (See example, Figure B-6.) SYST:COMM:GPIB:ADDR B.66 SYSTem:COMMunication:GPIB:ADDRess COMMAND Syntax: Short Form: SYST:COMM:GPIB:ADDR<INT VAL> 01 to 30 Long Form: SYSTem:COMMunication:GPIB:ADDRess<INT VAL> 01 to 30 Description: Sets selected power supply GPIB address.
Description: Enables (XON) or disables (NONE) data flow control via the serial interface (see PAR. 3.4.2.3) SYST:COMM:SER:PACE? B.75 SYSTEM:COMMUNICATION:SERIAL:PACE? QUERY Syntax: Short Form: SYST:COMM:SER:PACE? Long Form: SYSTem:COMMunication:SERial:PACE? Return Value: <int_value> (01 or 00 Description: Identifies whether data flow control via the serial interface is enabled (01 = XON) or disabled = NONE) (see PAR.
After sending a SYST:KLOC ON (local lockout enabled) command, all front panel controls (including pressing VOLTAGE and CURRENT adjustment knobs at the same time to return to local mode) are disabled. The power supply is now in the “local lockout” state and the status display reads .
been selected at the factory to permit the VISA demonstration program (which uses older command formats) to operate. SYST:LANG SCPI disables responses to older command formats. SYST:LANG? B.84 SYSTem:LANGuage? QUERY Syntax: Short Form: SYST:LANG? Long Form: SYSTem:LANGuage? Return Value: <string> SCPI or COMP Description: Identifies whether unit responds to older command formats.
Number (40) of locations programmable using *SAV and *RCL commands. SCPI Programming Language Strict interpretation of SCPI commands and queries. SYST:SET? B.91 SYSTem:SET? QUERY Syntax: Short Form: SYST:SET? Long Form: SYSTem:SET? Return Value: <comma separated string> Description: Returns comma-separated string indicating command functions in effect. See PAR. B.90 for command function definitions.
Page 108
TABLE B-4. ERROR MESSAGES (CONTINUED) ESR ERROR BIT SET ERROR MESSAGE EXPLANATION (SEE PAR. A.5) -221,”Settings conflict” E.g. , Invalid password from syst:pass:cen command. or Calibra- Execution error bit 4 tion state not enabled but CALibrate command received. -222,“Current, Voltage or Data out of Value (current or voltage) exceeds power supply rating or (data) Execution error bit 4 range”...
Page 110
How do I enter/exit Function mode? To enter a function, repeatedly press FUNCTION using a thin tool until status reads VIRT (vir- tual model, see below), ADDR (set GPIB address, PAR. 3.2.8), BAUD (set RS 232 baud rate, PAR. 3.2.9), M/S (Master/Slave, PAR. 3.2.10) or UTIL (utility, PAR.