2.3 Installation on unfinished walls
Installation in front of wall Vitodens 200 and 300
D
E
2
A
F
A Self-supporting mounting frame for
Vitodens incl. mounting bracket
B Ceiling mounting extension
(Vitodens)
C Self-supporting mounting frame for
wall mounted DHW cylinders incl.
ceiling fixing extension
54
C
B
G
D Wall mounted DHW cylinder (80 litres
capacity)
E Vitodens
F Mounting bracket for gas fired
combination boiler
G Mounting bracket for gas fired boiler
Self-supporting mounting frame
for Vitodens and wall mounted DHW
cylinders (80 litres capacity).
Suitable for wall mounting, for
self-supporting freestanding installation
or covering with various materials.
Incl. valves and gas angle valve G ¾" with
thermal safety shut-off valve.
H for gas fired combination boiler
with solder fittings
with compression fittings
H for gas fired boiler
with solder fittings
with compression fittings
Note regarding Vitodens 300 from 49 kW:
Vitodens 300 with 49 and 66 kW can also
be fitted to the self-supporting mounting
frame.
The boiler stands 20 mm proud on both
sides of the self-supporting mounting
frame.
The mounting bracket cannot be used
and the DHW cylinders to be hung
alongside the boiler are unsuitable for
Vitodens 300 with 49 and 66 kW.
VITODENS