Section III. Installation
OUTDOOR INSTALLATION
For outdoor installation with an exhaust grill, the heater must be placed in a suitable area on a level, noncombustible surface. Do not
install the heater under an overhang with clearances less than 3 feet from the top of the heater. The area under an overhang must be
open on three sides.
• In an outdoor installation it is important to ensure water is diverted from overhanging eves with a proper
gutter/drainage system. The heater must be set on a level foundation for proper drainage.
• Under certain conditions, "heavy rains or unusually high winds", it may be necessary to install an outdoors
vent. In this situation, use Outdoor Vent Kit, P/N 460424, (see below).
• This unit shall not be operated outdoors at temperatures below -20
SIDE VIEW
4 ft.
Window
Building

OUTDOOR VENT KIT

1.
Remove the six (6) retaining screws from the old exhaust grill and discard the screws, gasket, and exhaust grill as shown in
2. Install the Outdoor Vent Kit, (P/N 460424), as shown in
assembly, and heater cover are aligned before securing into place using the six (6) screws provided in the Outdoor Vent Kit.
GASKET
Figure 14.
If installing the heater next to or near an air conditioning unit or a heat pump, allow a minimum of 36 in.
between the air conditioning unit and the heater.
Rev. G • Rév. G 5-27-04
(Outdoor Shelter Installation in Canada, see
OUTDOOR INSTALLATION
VENTING GUIDELINES
Exhaust Grill
4 ft.
(Vent)
Heater
(side view)
Figure 13.
EXHAUST GRILL
SCREWS (6)
IMPORTANT!
C
4'
Vent Termination:
Must be at least 3 ft. above any forced
A
air inlet located within a 10 ft. radius.
Must be located 4 feet away from the building wall,
and at the following distances away from any door,
window, or gravity air inlet:
B
4 ft. below,
C
4 ft. horizontally, or
Check local building codes for setback requirements.
D
Figure
15. Make sure the holes in the gasket, metal flange of the main vent
CAUTION
o
F.
4'
B
3'
A
4'
Property Line
D
METAL FLANGE
SCREWS (6)
GASKET
17
page
14)
Figure
14.
Figure 15.
P/N • Réf. 472090