Recovering Data From The Flash-Backed Write Cache - HP ProLiant DL360e Gen8 Maintenance And Service Manual

Hide thumbs Also See for ProLiant DL360e Gen8:
Table of Contents

Advertisement

Remove the capacitor pack.
5.
Remove the capacitor pack holder.
6.
To replace the component, reverse the removal procedure.

Recovering data from the flash-backed write cache

If the server fails, use the following procedure to recover data temporarily stored in the FBWC.
CAUTION:
electrostatic discharge
Perform one of the following:
1.
Set up a recovery server using an identical server model. Do not install any internal drives or FBWC
o
in this server. (HP recommends this option.)
Find a server that has enough empty drive bays to accommodate all the drives from the failed server
o
and that meets all the other requirements for drive and array migration.
Before starting this procedure, read the information about protecting against
("Preventing electrostatic
discharge" on page 26).
Removal and replacement procedures 57