Recovering Data From The Flash-Backed Write Cache - HP ProLiant DL385p Maintenance And Service Manual

Gen8
Hide thumbs Also See for ProLiant DL385p:
Table of Contents

Advertisement

12 LFF or 25 SFF configuration
o
To replace the component, reverse the removal procedure.

Recovering data from the flash-backed write cache

If the server fails, use the following procedure to recover data temporarily stored in the FBWC.
CAUTION: Before starting this procedure, read the information about protecting against
electrostatic discharge.
Perform one of the following:
1.
Set up a recovery server using an identical server model. Do not install any internal drives or
o
FBWC in this server. (Hewlett Packard Enterprise recommends this option.)
Find a server that has enough empty drive bays to accommodate all the drives from the failed
o
server and that meets all the other requirements for drive and array migration.
Power down the failed server
2.
Transfer the drives from the failed server to the recovery server.
3.
Perform one of the following:
4.
If the array controller has failed, remove the cache module and capacitor pack from the failed
o
array controller, and install the cache module and capacitor pack on an identical array controller
model in the recovery server.
If the server has failed, remove the controller
o
module, and capacitor pack from the failed server, and install the controller, cache module, and
capacitor pack in the recovery server.
Power up the recovery server. If there was data in the cache at the time of the controller or server
5.
failure, a 1792 POST message appears, stating that valid data was flushed from the cache. This
data is now stored on the drives in the recovery server. You can now transfer the drives (and
controller, if one is used) to another server.
If the drives are migrated to different drive positions or there are volumes present in the recovery
server, a 1724 POST message appears, stating that logical drive configuration has been updated
automatically.
("Power down the
server" on page 25).
("Half-length expansion
board" on page 52), cache
Removal and replacement procedures 51