Page 1
User Manual Pressure • Temperature • Humidity • Air Velocity • Air Flow Flush-mount transmitter CPE 300 MODBUS system MODBUS system MODBUS system Remote control Remote control Remote control...
Channel selection With this selector, you can swap the transmission channel so that it matchs with the transmitter reception channel. See page 6 to configure the transmitter reception channel. Page 1 CPE 300 transmitter configuration via remote control / Modbus...
With the on-off switch located on the left top of the transmitter (when open), you can choose analogue output 0-10V (voltage) or 4-20 mA (current) Down 4-20 mA 0-10 V Page 2 CPE 300 transmitter configuration via remote control / Modbus...
Tw) 10 PSI 21 °F (humid temp. Tw) If the value measured is equal to 623 : 11 Pa 22 KJ/Kg (Enthalpy i) Résultat => 62.3 mmH O Page 3 CPE 300 transmitter configuration via remote control / Modbus...
(sequel) • Serial number of SPI sensing element Modbus code: 1402 Other access codes to different registers are indicated on each function at stage n°2. Shown as this pictogram: Page 4 CPE 300 transmitter configuration via remote control / Modbus...
Page 8
Once the folder is selected, press to validate. On the top left of each page of this manual, you can find a reminder of the configuration folder where the function is available. F400 Page 5 CPE 300 transmitter configuration via remote control / Modbus...
> • press twice to return to reading mode. • press once to return to another folder selection. • with keys to choose another sub-folder from the folder 100. Page 6 CPE 300 transmitter configuration via remote control / Modbus...
Page 10
> • press twice to return to reading mode. • press once to return to another folder selection. • with keys to choose another sub-folder from the folder 200. CPE 300 transmitter configuration via remote control / Modbus Page 7...
On the photo alongside, the multimeter is connected to the 0-10 V output. RS 232 connectors LCC 300 software Pressure connection Analogue Power supply Relays output terminal blocks Page 8 CPE 300 transmitter configuration via remote control / Modbus...
Page 12
> • press twice to return to reading mode. • press once to return to another folder selection. • with keys to choose another sub-folder from the folder 300. Page 9 CPE 300 transmitter configuration via remote control / Modbus...
300. After an analogue output setting, if the unit of measurement is modified (see page 5), you have to reconfigure the outputs according to the new unit of measurement. Page 10 CPE 300 transmitter configuration via remote control / Modbus...
Page 14
CPE 302 0 to ±500 0 to ±51 0 to ±2 0 to ±5 CPE 303 0 to 1000 ± 0 to ±102,0 0 to ±4,02 0 to ±10,00 Page 11 CPE 300 transmitter configuration via remote control / Modbus...
• press twice on to return to reading mode. • press once on to return to another folder selection. • with keys, you can choose another sub-folder from the folder 400. Page 12 CPE 300 transmitter configuration via remote control / Modbus...
Audible alarm Once the alarm is activated, an alarm sounds whilst the setpoint is reached. The BEEP alarm function must be activated to use the audible alarm. See page 12. Page 13 CPE 300 transmitter configuration via remote control / Modbus...
• press twice to return to reading mode. • press once to return to another folder selection. • with keys, you can choose another sub-folder from the folder 400. Page 16 CPE 300 transmitter configuration via remote control / Modbus...
If after having set up a setpoint, the unit of measurement is modified (see page 9), then you have to reconfigure the setpoints according to this new unit of measurement. Page 17 CPE 300 transmitter configuration via remote control / Modbus...
Page 21
• press twice to return to reading mode. • press once to return to another folder selection. • with keys , you can choose another sub-folder from the folder 400. Page 18 CPE 300 transmitter configuration via remote control / Modbus...
• press twice to return to reading mode. • press once to return to another folder selection. • with keys , you can choose another sub-folder from the folder 500. Page 19 CPE 300 transmitter configuration via remote control / Modbus...
• with keys , you can choose another sub-folder from the folder 500 Whenever you want, in reading mode, you can carry out a self-calibration by keeping “ESC” pressed Page 20 CPE 300 transmitter configuration via remote control / Modbus...
9.a- Activation / deactivation of the RS232 and home bus CPE 300 transmitters have one RS232 and one RS 485 digital output (Modbus protocol) - optional. With the RS 232, you can display 1 or 2 parameters which are measured by other Class 200 and 300 transmitters, or you can send measurements to be displayed on another Class 300 transmitters.
Step > • press twice to return to reading mode. • press once to return to another folder selection. • with keys, choose another sub-folder from the folder 300 Page 22 CPE 300 transmitter configuration via remote control / Modbus...
Page 26
> Step • press twice to return to reading mode. • press once to return to another folder selection. • with , choose another sub-folder from the folder 300. Page 23 CPE 300 transmitter configuration via remote control / Modbus...
01 to 9999 minutes Time-delay after purge from 00 to 60 seconds Code Description Available settings 1000 Measurement integration from 0 to 9 1002 Self-calibration for time-delay from 0 to 60 minutes Page 25 CPE 300 transmitter configuration via remote control / Modbus...
Page 29
2=> setpoint 1, time-delay and rising action 3=> setpoint 1, time-delay and falling action Setpoint 1 of Relay 2 Setpoint 2 of Relay 2 Time-delay on Relay 2 from 0 to 60 seconds Page 26 CPE 300 transmitter configuration via remote control / Modbus...
Page 30
NOTES... Page 25 CPE 300 transmitter configuration via remote control / Modbus...
Page 31
NOTES... Page 26 CPE 300 transmitter configuration via remote control / Modbus...
Need help?
Do you have a question about the CPE 300 and is the answer not in the manual?
Questions and answers