Kimo TG 100 Technical Data Sheet

Temperature transmitter

Advertisement

Quick Links

TG 100
duct mount
Part number
To order, just add the codes to complete the part number :
Transmitter / power supply / output
V
Active • 24 Vac/Vdc • 0-10V
A
Passive • 18/30 Vdc • 4-20 mA
Display
O
N
-
TG100
Example : TG100-VOA
Model : temperature transmitter TG 100 active sensor 0-10 V output, with
display and duct mount probe.
Dimensions of the housing
(with wall-mount plate)
Pt100 on terminal block
100 mm
Duct mount
100 mm
Technical Data Sheet
Pressure • Temperature • Humidity • Air Velocity • Airflow • Sound level
TG 100
Pt 100 on terminal block
(probe in option)
With display
Without display
A
Duct mount
B
Terminal block
42 mm
42 mm
150 mm
Ø 13 mm
Temperature transmitter
TG 100
• Duct temperature transmitter, TG100 type
• Measuring ranges from 0 to +50°C, -20 to +80°C, -50 to +50°C, 0 to +100°C,
0 to 200°C, 0 to +300°C, 0 to +400°C (according to model, see "Configuration")
• 0-10 V output , active sensor, power supply 24 Vac/Vdc (3-4 wires) or
4-20 mA output , passive loop, power supply 18 to 30 Vdc (2 wires)
• ABS IP 65 housing, with or without display
• Quick and easy mounting "1/4 turn" system with wall-mount plate

Features of the transmitter

Temperature
Working principle : Pt100 is a resistance with a positiv
coefficient which varies according to the temperature. The higher the
temperature is, the more the value of the resistance increases.
Example : for
0°C
Measuring range ......................see chart "Configuration"
Units of measurement .............°C, °F
Accuracy * ................................±0,5% of reading ±0,4°C
Response time .........................1/e (63%) 5 sec. (duct mount probe)
Resolution ................................0,1°C
Type of sensor..........................Pt 100 class A as per DIN IEC751
Type of fluid............................ air et neutral gases

Features of the housing

Housing ...............................................ABS
Fire-proof classification.....................HB as per UL94
Dimensions ........................................see drawings beside
Protection............................................IP 65
Display.................................................5- digit LCD. Dimensions 50 x 15 mm
Height of the digits .............................10 mm
Cable grip ............................................for cables Ø 7mm maxi.
Weight..................................................145g

Technical Specifications

Output / power supply....
..........................................
..........................................
..........................................
Consumption ....................................2 VA (0-10V) or max. 22 mA (4-20mA)
Electro-magnetical compatibility
Electrical connection .......................
Communication to PC ...................... Kimo RS 232 cable
Working temperature
(housing)
Working temperature
(probe)
Storage temperature ........................-10 to +70°C
Environment .....................................air and neutral gases
*All the accuracies indicated in this technical datasheet were stated in laboratories conditions, and can be guaranted for
measurements carried out in the same conditions, or carried out with calibration compensation.
100
- for 100°C
138,5
according to the probe (Pt 100 on terminal block)
according to the probe (Pt 100 on terminal block)
WITH or WITHOUT display
(with display)
active transmitter 0-10 V (power supply 24 Vac/Vdc ±10%), 3-4 wires
passive loop 4-20 mA (power supply. 18/30 Vdc), 2 wires
maximum load : 500 Ohms (4-20 mA)
minimum load : 1 K Ohms (0-10 V)
.......EN 61326
screw terminal block for cables Ø 1.5 mm² max
..........0 to +50°C
.............-20 to +80°C (duct mount probe)
according to the probe (Pt100 on terminal block)
e temperatur
e
(duct mount probe)
- 110g
(without display)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TG 100 and is the answer not in the manual?

Questions and answers

Summary of Contents for Kimo TG 100

  • Page 1: Technical Specifications

    TG100 Housing ..........ABS Example : TG100-VOA Fire-proof classification.....HB as per UL94 Model : temperature transmitter TG 100 active sensor 0-10 V output, with Dimensions ........see drawings beside display and duct mount probe. Protection..........IP 65 Display..........5- digit LCD. Dimensions 50 x 15 mm Dimensions of the housing Height of the digits ......10 mm...
  • Page 2 For the models • Output 0-10 V TG 100 - VOA, TG 100 - VNA, TG 100 - VOE, TG 100 - VNE active loop TG 100 - AOA, TG 100 - ANA, TG 100 - AOE, TG 100 - ANE 4 wires •...
  • Page 3 Configuration It is possible to configure the measuring ranges, the units, the output of the transmitter (according to the model) either by DIP switch and/or via software (connections on drawing “connection) Configuration by DIP switch To configure the transmitter, please unscrew the 2 screws from the housing, and then open it.