Page 1
INSTRUCTION MANUAL MICROCOMPUTER BASED TEMPERATURE INDICATING CONTROLLER FCR-13A Thank you for your purchase of our Microcomputer based Temperature Indicating Controller FCR-13A. This manual contains instructions for the mounting, functions, operations and notes when operating the FCR-13A. For your confirmation of the model and specifications of the units, peruse and make sure you have understood this instruction manual before starting operation.
Page 2
NOTES TO USERS FCR-13A ***** Note to users ***** Before operating this controller, make sure you have understood the following. Warning Turn the power supply to the instrument OFF before wiring or checking. Working or touching the terminal with the power switched ON may result in Electric Shock, which can cause severe injury or death.
CONTENTS FCR-13A --- CONTENTS --- 1 Model names Model names ----------------------------------------------------------------------------- 6 1.2 How to indicate the model name plate --------------------------------------------- 2 Name and functions of the sections 2.1 Names and displays -------------------------------------------------------------------- 2.2 Keys ----------------------------------------------------------------------------------------- 10 3 Setup 3.1 Taking the internal assembly out ----------------------------------------------------- 11 3.2 Switch setting (multi-function) --------------------------------------------------------- 11 3.3 Insertion of the internal assembly ---------------------------------------------------- 14 4 Operations...
Page 4
CONTENTS FCR-13A Communication protocol-------------------------------------------------------------- 27 (5) Auxiliary function setting mode 2 Scaling high limit value setting ------------------------------------------------------ 28 Scaling low limit value setting ------------------------------------------------------- 28 Decimal point place selection ------------------------------------------------------- 28 PV filter time constant setting ------------------------------------------------------- 29 Main output high limit setting -------------------------------------------------------- 29 Main output low limit setting --------------------------------------------------------- 29 Main output ON/OFF action hysteresis setting --------------------------------- 29 Cooling action mode selection ------------------------------------------------------ 30...
Page 5
CONTENTS FCR-13A 6 Running 6.1 When using the FCR-13A as a Temperature controller ------------------------- 42 6.2 When using the FCR-13A as a Simplified program controller ----------------- 43 7 Action explanations 7.1 Standard action drawings --------------------------------------------------------------- 44 7.2 Heater burnout alarm action drawing ------------------------------------------------ 44 7.3 ON/OFF action drawings ---------------------------------------------------------------- 45 7.4 Pattern end action drawing ------------------------------------------------------------- 45 7.5 Heating•Cooling action drawings...
MODEL NAME FCR-13A 1. Model names 1.1 Model names Standard models F C R – 1 3 A – Series name: FCR-130 Control action PID control (*1) Alarm Alarm action (*2) Relay contact output Output Non-contact voltage output Current output Input Multi-range input (*3) *1: Fuzzy self-tuning PID, PID, PD and ON/OFF action are selectable by internal DIP...
MODEL NAME FCR-13A Code Specification 24Vdc Insulated power output Dust-proof•Drip-proof (See page 70 and 71 for the contents of the options in detail.) Warning Do not take the inner assembly out nor touch the terminal with the power supply on. Touching the terminal with the power switched ON may result in Electric Shock, which can cause severe injury or death.
NAME AND FUNCTIONS OF THE SECTIONS FCR-13A 2 Name and functions of the sections 2.1 Names and Displays (11) (12) (13) (14) (15) (10) (16) (17) [Fig. 2.1-1] (1) PV display Indicates the Process variable (PV) with red LED. (2) SV display Indicates the Setting value (SV), Manipulating value (MV) or Time (TIME) with green LED.
Page 9
NAME AND FUNCTIONS OF THE SECTIONS FCR-13A (8) Control output or Heating output action indicator (OUT 1 The green LED is lit when the Control output or Heating output is on. (For the current output type, it blinks corresponding to the manipulating value at 0.125 seconds of period.) (9) Cooling output action indicator (OUT 2 ) [Option]...
NAME AND FUNCTIONS OF THE SECTIONS FCR-13A 2.2 Keys Main functions are described below, however, the keys have other functions in various modes. Refer to Section 4.1 Operating flow chart (Page 15ff). Increase key : Increases the numeric value on the SV display during setting mode.
SETUP FCR-13A 3. Setup 3.1 Taking the internal assembly out Before the power supplied to this instrument is on, take the internal assembly out from the case by pushing the hook (bottom of the instrument) in the direction indicated by the arrow and holding the notches.
Page 12
SETUP FCR-13A The following items can be designated by the DIP switch (SW304). Factory adjusted as all switches OFF [ [Table 3.2-1] Item Designation Switch status Sw. No Fuzzy self-tuning PID action No.1: OFF No.2: OFF PID action No.1: ON No.2: OFF Control action PD action...
Page 13
SETUP FCR-13A Select the sensor type by rotary switch sensor input (SW303). Factory adjusted as K, [ [Table 3.2-2] Rotary Sw. DIP Sw. Type of Scale range No. 7 sensor -200 to 1370 -320 to 2500 -200 to 1000 -320 to 1800 0 to 1760 0 to 3200 0 to 1820...
SETUP FCR-13A The alarm action type and the pattern end output when program control can be designated by the rotary switch A1 (SW302) and A2 (SW301). The rotary switch A2 (SW301) is equipped only when the option A2 is applied. Rotary switch A1 (SW302): Alarm 1 (A1) action or Pattern end 1 output.
OPERATIONS FCR-13A 4 Operations 4.1 Operating flow chart Instrument power ON Warm-up status (For approx. 2s, displays as shown on page 18.) Control output OFF function Manual control PV/SV display mode Output manipulating value Step rest time [Main setting mode] [Sub setting mode] Main setting Setting value memory No.
Page 16
OPERATIONS FCR-13A : Options : Press the key while the key is being pressed. 3s: Press the key for approx. 3 seconds while the key is being pres sed. 3s: Press the key for approx. 3 seconds while the keys are being pressed. 3s : Pressing the key, press the key for approx.
Page 17
OPERATIONS FCR-13A Set the temperature of the program in the Sub setting mode, Auxiliary function setting mode 1 and 2. [Program mode] Alarm 1 (A1) action Main setting value Program control delayed timer setting rising rate setting change Alarm 2 (A2) action Main setting value Step 1 time setting delayed timer setting...
Page 18
OPERATIONS (PV/SV display mode) FCR-13A 4.2 Operations The PV display indicates the sensor type and the SV display indicates the rated value selected by Sensor input designation (page 12, 13) for approx. 2 seconds after the power is turned on. See [table 4.2-1]. During this time, all outputs and LED indicators are in their off status.
OPERATIONS (Main, Sub setting mode) FCR-13A (2) Main setting mode In the PV/SV display mode, if the key is pressed, the Main setting mode will be selected. The setting value can be increased or decreased by pressing the keys. If the key is pressed, the setting value will be registered and the controller will revert to the PV/SV display.
OPERATIONS (Sub setting mode) FCR-13A (Auto-tuning Cancel) (Auto-tuning Perform) [Factory adjusted as Auto-tuning Cancel] If the Auto-tuning is released during the process, the PID value reverts to the former value. Main proportional band setting Mode to set the proportional band for Main control. Setting value Setting range: 0.1 to 999.9% [Factory adjusted as 2.5%]...
OPERATIONS (Sub setting mode) FCR-13A Main control Mode to set the proportional cycle of Main control. proportional cycle setting Setting range: 1 to 120s Setting value [Factory adjusted as 30s to Relay contact output type, and 3s to Non-contact voltage output type] This setting item is not available to Current output type.
OPERATIONS (Sub setting mode) FCR-13A Alarm 1 (A1) setting Mode to set the action point of the Alarm 1 (A1) Setting value output. This item is not displayed if setting the rotary switch to No. 0 or No. 7 (See page 14.) Setting range: See [table 4.2-2].
OPERATIONS (Sub setting mode) FCR-13A Setting the value to 0.0 disables the function. It is recommended to set approx. 80% of the Heater current value considering the voltage fluctuation. Self-holding is not available to the alarm output. Loop break alarm Mode to set the time for Loop break alarm time setting activation assessment.
Page 24
OPERATIONS (Auxiliary function setting mode 1) FCR-13A (4) Auxiliary function setting mode 1 In PV/SV display mode, if the key is pressed for approx. 3 seconds while the key is being pressed, Auxiliary function setting mode 1 can be selected. The setting value can be increased or decreased by pressing the keys.
OPERATIONS (Auxiliary function setting mode 1) FCR-13A As to the Lock mode 3 When using the FCR-13A as a Fixed value controller. The setting values can temporarily be changed by the selected setting value memory number, however, when the number is changed, the setting values changed by the previous number are canceled and returns to the former values.
OPERATIONS (Auxiliary function setting mode 1) FCR-13A Sensor correction function Corrects the input value from the sensor. When a sensor cannot be set at a location where control is desired, the se nsor measuring temperature may deviate from the temperature i n the controlled location.
This display is available only when the option [C or C5] is applied. Communication protocol Mode to select a communication protocol. Selectio [Factory adjusted as Shinko standard protocol Based on Modbus, ASCII mode This display is available only when the option [C or C5] is applied. PV/SV display mode Actual...
OPERATIONS (Auxiliary function setting mode 2) FCR-13A (4) Auxiliary function setting mode 2 In PV/SV display mode, if the key is pressed for approx. 3 seconds while the keys are being pressed, Auxiliary function setting mode 2 can be selected. The setting value can be increased or decreased by pressing the keys.
OPERATIONS (Auxiliary function setting mode 2) FCR-13A PV filter time constant Mode to suppress the PV fluctuation caused by Setting such as disturbance. Setting valu Set the value larger by degrees, and find the setting value at which the value does not fluctuate. If the value is set too large, it affects control result due to the delay of response.
OPERATIONS (Auxiliary function setting mode 2) FCR-13A Cooling action mode selection Mode to select the Cooling action, Selection Air cooling, Oil cooling or Water cooling. [Factory adjusted as Air cooling] This display is indicated only when the option [D ] is applied.
OPERATIONS (Auxiliary function setting mode 2) FCR-13A Alarm 1 (A1) action Mode to select the action Energized or Deenergized Energized/Deenergized for Alarm 1. Selection [Factory adjusted as Energized] This display is not indicated when the rotary switch is set to No. 0 or No.
OPERATIONS (Auxiliary function setting mode 2) FCR-13A Alarm 1 (A1) action Mode to set the action delayed timer for Alarm 1. delayed timer setting Setting range: 0 to 9999s Setting valu [Factory adjusted as 0s] Alarm output is turned on when the setting time has passed after the input gets into the alarm output range.
OPERATIONS (Auxiliary function setting mode 2) FCR-13A Transmission output selection Mode to select the type of Transmission output. Selection [Factory adjusted as PV transmission] This display is indicated only when the option [TA or TV] is applied. Process variable (PV) transmission Main setting value (SV) transmission Manipulating value (MV) transmission Transmission output...
OPERATIONS (Auxiliary function setting mode 2) FCR-13A Display selection when Mode to select the display when the control output control output is off is off. Selection [Factory adjusted as indicating OFF on the PV display] OFF is indicated on the PV display. No indication (all unlit).
Page 35
OPERATIONS (Auxiliary function setting mode 2) FCR-13A Output selection when Mode to select the control output OFF or not when input burnou DC input is over scale or under scale. Selected value Control output OFF Control output ON [Factory adjusted as Control output PV/SV display mode Actual Main setting...
OPERATIONS (Program mode) FCR-13A (6) Program mode In PV/SV display mode, if the key is pressed for approximately 3 seconds while key is being pressed, the Program mode can be selected. The setting value can be increased or decreased by pressing the keys.
Page 37
OPERATIONS (Program mode) FCR-13A PV/SV display mode Actual Main setting temperature value for approx. 3s Program control change Control form is changed between Fixed value and Program. Setting value of fixed value control In Fixed value control, if the key is pressed, (Fixed value the mode will revert to the PV/SV display mode.
OPERATIONS (Auto/Manual control change) FCR-13A Step 5 Time setting Mode to set the Time for step 5. Setting value [The setting range and the factory adjusted value are the same as Step 1.] Step 6 Time setting Mode to set the Time for step 6. Setting value [The setting range and the factory adjusted value are the same as Step 1.]...
OPERATIONS (Control output OFF function) FCR-13A (8) Control output OFF function A function to turn the control output OFF even if the power to the instrument is supplied. The function is used when required to halt the control action or when the FCR-13A is not being used in multiple controllers.
OPERATIONS (Manipulating value and Step time indication ) FCR-13A (9) Output manipulating value and Step rest time indication mode In the PV/SV display mode, press the key for approx. 3 seconds. The display will be changed to main setting mode in the process, however, keep pressing it until the Output manipulating value is displayed.
SETTING VALUE MEMORY FUNCTION FCR-13A 5. Setting value memory function [Option code: SM] If the option SM is applied, a maximum of 7 files of data can be memorized, and when selecting a desired file, the desired control can be performed. In one (1) file are 14 kinds of data: Main setting value, PID each value, Cooling control proportional band value, Alarm setting values (A1 to A4), Overlap band/Dead band value, Main output high limit, Main output low limit, Cooling output high limit and Cooling...
RUNNING FCR-13A 6 Running After the controller has been mounted to the control panel and wiring is completed, it can be started in the following manner. 6.1 When using the FCR-13A as a Temperature controller (1) Turn the power supply to the FCR-13A ON. For approx.
RUNNING FCR-13A 6.2 When using the FCR-13A as a Simplified program controller (1) Turn the power supply to the FCR-13A ON. For approx. 2s after the power is turned ON, the type of sensor and the unit designated in Sensor input designation (page 12, 13) are indicated on the PV display, and the rated maximum value is indicated on the SV display.
ACTION EXPLANATIONS FCR-13A 7.3 ON/OFF action drawings Action Heating (reverse) action Cooling (direct) action Hysteresis Hysteresis Control action Main setting Main setting 12Vdc 0Vdc 0Vdc 12Vdc Output 20mAdc 4mAdc 4mAdc 20mAdc Indicator [OUT1] Green Unlit Unlit part: Acts ON or OFF. 7.4 Pattern end action drawing Pattern end output is Program control end...
ACTION EXPLANATIONS FCR-13A 7.5 Heating•Cooling action drawings [Option D ] Heating (reverse) action in Heating control Heating P-band (Cooling P-band) Heating (Cooling) Action Setting Relay contact (*1) Heating Non-contact 12Vdc 0Vdc 12/0Vdc output voltage (*1) 20mAdc 4mAdc 20 to 4mAdc Current (*2) Indicator...
Page 47
ACTION EXPLANATIONS FCR-13A Cooling (direct) action in Heating control (Heating P-band) Cooling P-band (Heating) Cooling Action Setting Relay contact (*1) Cooling Non-contact 0Vdc 12Vdc 0/12Vdc output voltage (*1) 4mAdc 20mAdc 4 to 20mAdc Current (*2) Indicator Unlit [OUT2] Yellow (*1) Cycle action is performed according to deviation. (*2) Changes continuously according to deviation.
ACTION EXPLANATIONS FCR-13A Heating (reverse) action in Cooling control (Cooling P-band) Heating P-band (Cooling) Heating Action Setting Relay contact (*1) Heating Non-contact 0Vdc 0/12Vdc 12Vdc output voltage (*1) 4mAdc 20mAdc 4 to 20mAdc Current (*2) Indicator [OUT1] Green Unlit (*1) Cycle action is performed according to deviation. (*2) Changes continuously according to deviation.
Page 49
ACTION EXPLANATIONS FCR-13A Cooling (direct) action in Cooling control Cooling P-band (Heating P-band) Cooling (Heating) Action Setting Relay contact (*1) Cooling Non-contact 12Vdc 0Vdc 12/0Vdc output voltage (*1) 20mAdc 4mAdc 20 to 4mAdc Current (*2) Indicator Unlit [OUT2] Yellow (*1) Cycle action is performed according to deviation. (*2) Changes continuously according to deviation.
ACTION EXPLANATIONS FCR-13A When setting Dead band Action Heating action Cooling action Proportional band Dead band Proportional band Control action Setting Relay contact (*1) (*1) Non- contact 12Vdc 12/0Vdc 0Vdc 0Vdc 12Vdc 0/12Vdc Output voltage (*1) (*1) 20mAdc 4mAdc 4mAdc 20mAdc 20 to 4 mAdc 4 to 20mAdc...
ACTION EXPLANATIONS FCR-13A When setting Overlap band with Relay contact output. Heating proportional band Cooling proportional band Overlap band Control action Setting Heating output (*1) Relay contact output Cooling output (*1) Indicator [OUT1] Green Unlit Indicator [OUT2] Yellow Unlit (*1) Cycle action is performed according to deviation.
CONTROL ACTIONS FCR-13A 8. Control actions 8.1 Fuzzy self-tuning Fuzzy self-tuning is a function to perform a fine adjustment of PID values automatically. The stable control can be carried out even if the conditions of the process are changed due to things like change in types and rates of production.
CONTROL ACTIONS FCR-13A 8.2 Explanations of PID (1) Proportional band (P) Proportional action is the action which the control output varies in proportion to the deviation between the setting value and the processing temperature. If the proportional band is narrowed, even if the output changes by a slight variation of the processing temperature, better control results can be obtained as the offset decreases.
CONTROL ACTIONS FCR-13A 8.3 PID auto-tuning of this controller In order to decide each value of P, I, D and ARW automatically, this system gives the fluctuation to the controlling object by force. (1) When the difference between setting value and processing temperature is large when the temperature rises.
OTHER FUNCTIONS FCR-13A 9. Other functions (1) Burnout alarm (Upscale) When the thermocouple or RTD is burnt out or the input value exceeds [Rated scale maximum value +1% of rated scale span], the control output is turned OFF(main output low limit value for the current output type) and the PV display blinks [ With the input RTD Pt100 ( ), if the input value is greater than 999.9, the PV display blinks [...
MOUNTING TO CONTROL PANEL FCR-13A 10. Mounting to control panel 10.1 Site selection Mount the controller in a place with: (1) A minimum of dust, and an absence of corrosive gases. (2) No mechanical vibrations or shocks. (3) No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 ) that does not change suddenly.
MOUNTING TO CONTROL PANEL FCR-13A 10.3 Panel cutout drawing +0.5 n x 48-3 Lateral close mounting n: Number of units mounted +0.5 [Fig. 10.3-1] 10.4 Current transformer (CT) dimension drawing CTL-6-S (for 20A) CTL-12-S36-10L1 (for 50A) [Fig. 10.4-1]...
MOUNTING TO CONTROL PANEL FCR-13A 10.5 Mounting • When using the One-touch type mounting bracket Mounting panel thickness is 1 to 3mm. Mount one-touch mounting bracket 1 to the body in advance, and then Insert the FCR-13A 2 from the front of the panel.
WIRING CONNECTION FCR-13A 11. Wiring connection Warning Turn the power supply to the instrument off before wiring or checking. Working or touching the terminal with the power switched on may result in Electric Shock, which can cause severe injury or death Moreover, the instrument must be grounded before the power supply to the instrument is turned on.
WIRING CONNECTION FCR-13A n Recommended terminal Use a solderless terminal with insulation sleeve to fit to M3 screw as shown below. 3.2mm 3.2mm Solderless Manufacturer Model name Tightening torque terminal Nichifu Terminal Industries CO.,LTD. 1.25Y-3 Y type 0.6N•m (6kgf•cm) Japan Solderless Terminal MFG CO.,LTD. VD1.25-B3A Max.
Page 63
Thermocouple Electric furnace [Fig. 11.2-2] The connectable SSRs in parallel are 4 units if the Shinko SSRs (SA-200 series) are used. AC or DC is available to supply voltage 24V, however, do not confuse the polarity when DC is applied.
Page 64
WIRING CONNECTION FCR-13A • Current transformer (CT1, CT2) input [Option code: W, W3] (1) This alarm is not available for detecting current under phase control. (2) Use current transformer (CT) an accessory one, and pass one lead wire of heater circuit into the hole of the CT. (3) When wiring, keep CT wire away from AC source and load wire to avoid the interference from external.
SPECIFICATIONS FCR-13A 12. Specifications 12.1 Standard specifications Mounting method : Flush Setting : Input system using membrane sheet key Display PV display : Red LED display 4 digits, size, 8(H) x 4(W)mm SV/MV/TIME display : Green LED display 4 digits, size, 8(H) x 4(W)mm Setting value memory number (MEMO) display: Yellow LED display 1 digit, size, 8(H) x 4(W)mm Indicating accuracy...
Page 66
SPECIFICATIONS FCR-13A Voltage : 0 to 1Vdc Input impedance, 1M or greater Allowable input voltage, 5V or less Allowable signal source resistance, 2k or less In the case of input burnout, Upscale Supply voltage : 100 to 240Vac 50/60Hz, 24Vac/dc 50/60Hz Allowable voltage fluctuation: 100 to 240Vac: 85 to 264Vac 24Vac/dc...
Page 67
SPECIFICATIONS FCR-13A Reset : ±Proportional band converted value When thermocouple or RTD input, –199.9 to 999.9 When DC input, –1999 to 9999 (Decimal point place follows the selection.) Output limiter : 0 to 100% (In the case of Current output, –5 to 105%) ON/OFF action Hysteresis setting range : When thermocouple or RTD input, 0.1 to 100.0...
Page 68
SPECIFICATIONS FCR-13A Circuit insulation configuration Ground terminal Isolated Power source Isolated Isolated Isolated Main output Communication part (*2) Non-isolated Isolated Isolated (*1) Input Transmission Cooling output, output Alarm 2 output or CT input Loop break alarm output Non-isolated External setting Isolated Setting value input...
Page 69
SPECIFICATIONS FCR-13A Power consumption: Approx. 15VA Ambient temperature : 0 to 50 (32 to 122 ) Ambient humidity : 35 to 85%RH (non-condensing) Weight : Approx. 320g External dimension: 48 x 96 x 100mm (W x H x D) Material : Base and Case, Flame resisting resin Color : Base and Case, Light gray...
SPECIFICATIONS FCR-13A 12.2 Optional specifications Alarm 2 output [A2] The alarm action point is set by ±deviation to main setting (except Process value alarm). [When the alarm action is set as energized] When the input exceeds the range, the output turns ON or OFF (in the case of High/Low limit range alarm) [When the alarm action is set as deenergized] The output acts conversely...
Page 71
SPECIFICATIONS FCR-13A Output [DR] Relay contact 1a Control capacity, 250Vac 3A (resistive load) 250Vac 1A (inductive load cosø=0.4) [DS] Non-contact voltage (for SSR drive) Vdc maximum 40mAdc (short circuit protected) [DA] Current 4 to 20mAdc (Isolation type) Load resistance: Maximum 550 Cooling action mode selection function: Key selectable, Air cooling (Linear characteristic), Oil cooling (1.5th Power of characteristic) or Water cooling...
Page 72
SPECIFICATIONS FCR-13A Serial communication [C or C5] The following operations can be executed from the external computer. (1) Reading and setting of the Main setting value, PID values and various setting values (2) Reading of the input value and the action status. (3) Change of the functions Communication circuit Based on EIA RS-485 [Option code: C5]...
Page 73
SPECIFICATIONS FCR-13A External setting [EA or EV] Main setting value can be set by external analog signal. Setting signal : Current [EA] 0 to 20mAdc, 4 to 20mAdc Input impedance, 50 (non-isolated with input) : Voltage [EV] 0 to 1Vdc, 1 to 5Vdc Allowable input voltage, 5V or less Input impedance, 100k (non-isolated with input)
Page 74
SPECIFICATIONS FCR-13A Insulated power output [P24] Can be used as a small capacity power source for each sensor and converter. The insulated power output (P24) is not available with a combination of Alarm 2 output (A2), Heating/Cooling control output (D ) or Loop break alarm output (LA).
TROUBLESHOOTING FCR-13A 13. Troubleshooting If any malfunctions occur, refer to the following items after checking the power and the wiring. Warning Turn the power supply to the instrument off before wiring or checking. Working or touching the terminal with the power switched on may result in Electric Shock, which can cause severe injury or death.
Page 76
TROUBLESHOOTING FCR-13A <Indication> Phenomenon Presumed cause and the action • Designation of the Sensor input is improper. Set the Sensor input properly by the Rotary switch (SW303) and the DIP switch (SW304). (page 12, 13) If indication • Temperature unit ( ) is mistaken.
Page 77
TROUBLESHOOTING FCR-13A <Control> Phenomenon Presumed cause and the action • Thermocouple or RTD is burnt out. [In the case of Thermocouple] If the input terminal of the instrument is connected, and if nearby room temperature is indicated, the instrument should be normal and sensor may be burnt out.
CHARACTER TABLE FCR-13A 14. Character table <Main setting mode> Character Item Initial Data Main setting <Sub setting mode> Character Item Initial Data Setting value memory number Auto-tuning Perform/Cancel - - - -: Cancel Main proportional band 2.5% Cooling proportional band 1.0 times Integral time setting 200s...
Page 79
CHARACTER TABLE FCR-13A <Auxiliary function setting mode 1> Character Item Initial Data Setting value lock designation - - - -: Unlock Main setting value high limit Main setting value low limit Sensor correction setting Overlap band/Dead band setting Remote/Local change : Local Instrument number setting Transfer rate selection...
Page 80
CHARACTER TABLE FCR-13A Character Item Initial Data External setting high limit External setting low limit Transmission output selection PV transmission Transmission output high limit Transmission output low limit Display selection when control output is off Main setting value rising rate 0 /minute Main setting value falling rate 0 /minute...
Page 84
For any inquiries about this unit, please contact the sho where you purchased the unit after checking the followin [Example] • Model --------------------------- FCR-13A-R/M • Type of input ------------------ K • Option --------------------------- A2, TV, C5, W(20A) • Instrument number ---------- No. xxxxxx...