Mitsubishi PE-10MYC Data Book page 77

Pe(h) series air-cooled split-type ducted air conditioners
Table of Contents

Advertisement

PEH-7,8,10MYA-EU
PEH-15,20MYA-EU
COMPRESSOR OVER CURRENT RELAY
COMPRESSOR INTERNAL THERMOSTAT
HIGH PRESSURE SWITCH
FROST PROTECTOR
INDOOR FAN MOTOR OVER CURRENT RELAY
INDOOR FAN MOTOR INTERNAL THERMOSTAT
OUTDOOR FAN MOTOR OVER CURRENT RELAY
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT
FUSE
COMPRESSOR OVER CURRENT RELAY
COMPRESSOR INTERNAL THERMOSTAT
HIGH PRESSURE SWITCH
FROST PROTECTOR
INDOOR FAN MOTOR OVER CURRENT RELAY
OUTDOOR FAN MOTOR OVER CURRENT RELAY
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT
FUSE
ITEM
ITEM
PEH-5MYA-EU
NO.
PUH-5MYE-EU
51C
15.0A
49C
110 ± 5˚C OFF
61 ± 9˚C ON
63H
26D1
26D2
51F1
3.5A
-
51F2
-
F1
3
PEH-10MYA-EU
PUH-10MYC
-EU
NO.
1
PUH-10MYE-EU
51C1,2
31.0A
49C
63H
26D1
26D2
51F1
5.0A
51F
-
F1
3
- 76 -
PEH-8MYA-EU
PEH-7MYA-EU
PUH-8MYC1-EU
PUH-7MYC1-EU
PUH-8MYE-EU
19.0A
105 ± 5˚C OFF
83 ± 11˚C ON
2.94MPa OFF
-12 ± 2 ˚C ON
6 ± 2 ˚C OFF
5.0A
150˚ C OFF
2.5A
150˚C OFF
3.15A
PEH-15MYA-EU
PEH-20MYA-EU
PUH-15MYC
-EU
PUH-20MYC
1
22.0A
105 ± 5 ˚ C OFF 83 ± 11˚C ON
2.94MPa OFF
-12 ± 2 ˚C ON
6 ± 2 ˚C OFF
4.6A
2.5A
150˚ C OFF
3.15A
22.0A
3.5A
-EU
1
31.0A
7.2A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents