Obh532E - Mitsubishi Electric MUZ-GE25VA-a1 Service Manual

Split-type air conditioners
Table of Contents

Advertisement

3. Outdoor unit failure mode table
The upper
lamp of
OPERATION
Abnormal point
INDICATOR
(Failure mode / protection)
lamp
(Indoor unit)
11-time fl ash
DC voltage
2.5 seconds
OFF
Each phase current of
compressor
12-time fl ash
Overcurrent Compressor
2.5 seconds
open-phase
OFF
14-time fl ash
Stop valve (Closed valve)
2.5 seconds
OFF
4-way valve/
Pipe temperature
(VAD)
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
11-3. TROUBLESHOOTING CHECK TABLE
No.
Symptom
LED indication
Outdoor unit
1-time fl ash every
does not op-
2.5 seconds
1
erate.
2
3
6-time fl ash
4
2.5 seconds OFF
11-time fl ash
5
2.5 seconds OFF
14-time fl ash
2.5 seconds OFF
6
16-time fl ash
2.5 seconds OFF
7
(VAD)
'Outdoor unit
2-time fl ash
stops and
2.5 seconds OFF
restarts 3
8
minutes later'
is repeated.
3-time fl ash
2.5 seconds OFF
9
4-time fl ash
2.5 seconds OFF
10
5-time fl ash
2.5 seconds OFF
11
8-time fl ash
12
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
13
12-time fl ash
14
2.5 seconds OFF
13-time fl ash
15
2.5 seconds OFF

OBH532E

1.
Intelligent power module (IPM): MUZ-GE25VA -
IGBT module (IC700): MUZ-GE60/71/80VAD
Power module (IPM): Other models
LED indication
(Outdoor P.C. board)
8-time fl ash
DC voltage of inverter cannot be
2.5 seconds OFF
detected normally.
9-time fl ash
Each phase current of compressor
2.5 seconds OFF
cannot be detected normally.
10-time fl ash
Large current fl ows into the intelligent
2.5 seconds OFF
power module (IPM)/ IGBT module
(IC700)/ power module (IPM). 1.
The open-phase operation of
compressor is detected.
The interphase short circuit occurs
in the output of the intelligent power
module (IPM)/ IGBT module (IC700)/
power module (IPM). 1.
14-time fl ash
Closed valve is detected by
2.5 seconds OFF
compressor current.
16-time fl ash
The 4-way valve does not work
2.5 seconds OFF
properly.
The indoor coil thermistor detects an
abnormal temperature.
Abnormal point/
Condition
Outdoor power sys-
Overcurrent protection cut-out operates 3 consecutive times
tem
within 1 minute after the compressor gets started.
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
defrost thermistor, outdoor heat exchanger temperature ther-
mistor, P.C. board temperature thermistor or ambient tempera-
ture thermistor shorts or opens during compressor running.
Outdoor control sys-
Nonvolatile memory data cannot be read properly.
tem
(The upper lamp of OPERATION INDICATOR lamp of the in-
door unit lights up or fl ashes 7-time.)
Serial signal
The communication fails between the indoor and outdoor unit
for 3 minutes.
Stop valve/
Closed valve is detected by compressor current.
Closed valve
Outdoor unit
Outdoor unit is defective.
(Other abnormality)
4-way valve/
The 4-way valve does not work properly.
Pipe temperature
The indoor coil thermistor detects an abnormal temperature.
Overcurrent protec-
Large current fl ows into the intelligent power module (IPM)/
tion
IGBT module (IC700)/ power module (IPM). 1.
Discharge tempera-
Temperature of discharge temperature thermistor exceeds
ture overheat protec-
116°C, compressor stops. Compressor can restart if discharge
tion
temperature thermistor reads 100°C or less 3 minutes later.
Fin temperature
Temperature of fi n temperature thermistor on the heat sink
/P.C. board tem-
exceeds 75 ~ 80°C or temperature of P.C. board temperature
perature thermistor
thermistor on the inverter P.C.board exceeds 70 ~ 75°C.
overheat protection
High pressure pro-
Temperature of indoor coil thermistor exceeds 70°C in HEAT
tection
mode. Temperature of outdoor heat exchanger temperature
thermistor exceeds 70°C in COOL mode.
Compressor synchro-
The waveform of compressor current is distorted.
nous abnormality
Outdoor fan motor
Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
Each phase current
Each phase current of compressor cannot be detected nor-
of compressor
mally.
DC voltage
DC voltage of inverter cannot be detected normally.
Condition
Refer to 11-5. "How
to check inverter/
compressor".
Reconnect
compressor connector.
Refer to 11-5.
to check inverter/
compressor".
Check the stop valve
Check 4-way valve.
Replace inverter P.C.
board.
Condition
69
, MUZ-GE35/50VA
A1
Indoor/outdoor
unit failure
Remedy
mode recall
recall function
function
"How
Remedy
Reconnect connector of compressor.
Refer to 11-5.
"How to check in-
verter/compressor".
Check the stop valve.
Refer to 11-5.
"Check of outdoor
thermistors".
Replace the inverter P.C. board.
Refer to 11-5.
"How to check mis-
wiring and serial signal error.
Check the stop valve.
Refer to 11-2.2. "Flow chart of the
detailed outdoor unit failure mode
recall function".
Refer to 11-5.
"Check of R.V.
coil".
Replace the inverter P.C. board.
Reconnect the connector of the com-
pressor.
Refer to 11-5.
"How to check in-
verter/compressor".
Check the stop valve.
Check the refrigerant circuit and
the refrigerant amount.
Refer to 11-5.
"Check of LEV".
Check around the outdoor unit.
Check the outdoor unit air passage.
Refer to 11-5.
"Check of outdoor
fan motor".
Check the refrigerant circuit and
the refrigerant amount.
Check the stop valve.
Reconnect connector of compressor.
Refer to 11-5.
"How to check in-
verter/compressor".
Refer to 11-5.
"Check of outdoor
fan motor.
Refer to 11-5.
"Check of inverter
P.C. board.
Refer to 11-5.
"How to check in-
verter/compressor".
Refer to 11-5.
"How to check in-
verter/compressor".
Outdoor unit
failure mode