ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Outdoor unit
Model
precharged
MUZ-GE25VA
MUZ-GE25VAD
MUZ-GE33VA
MUZ-GE35VA
MUZGE35VA2
MUZGE35VAD
1,150
MUZ-GE42VA
MUZ-GE42VAD
Calculation: X g = 30 g/m × (Refrigerant piping length (m) - 7)
Outdoor unit
Model
precharged
MUZ-GE50VA
MUZ-GE50VA2
1,550
MUZ-GE50VAD
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7)
Outdoor unit
Model
precharged
MUZ-GE60VA
1,550
MUZ-GE60VAD
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 10)
Outdoor unit
Model
precharged
MUZ-GE71VA
MUZ-GE71VAD
MUZ-GE80VA
1,900
MUZ-GE80VA2
MUZ-GE80VAD
Calculation: X g = 55 g/m × (Refrigerant piping length (m) – 10)
NOTE: Refrigerant piping exceeding 7 m (MUZ-GE25/33/35/42/50) or 10 m (MUZ-GE60/71/80) requires additional
refrigerant charge according to the calculation.

OBH532E

5 m
6 m
800
0
0
7 m
0
7 m
0
7 m
0
Refrigerant piping length (one way)
7 m
8 m
9 m
10 m
0
30
60
90
Refrigerant piping length (one way)
10 m
15 m
60
160
Refrigerant piping length (one way)
10 m
15 m
0
100
Refrigerant piping length (one way)
10 m
15 m
0
275
30
11 m
12 m
13 m
14 m
120
150
180
210
20 m
25 m
260
360
20 m
25 m
200
300
20 m
25 m
550
825
15 m
20 m
240
390
30 m
460
30 m
400
30 m
1,100

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents