3. Outdoor unit failure mode table
The upper
lamp of
OPERATION
Abnormal point
INDICATOR
(Failure mode / protection)
lamp
(Indoor unit)
OFF
None (Normal)
1-time fl ash
Indoor/outdoor
2.5 seconds
communication, receiving
OFF
error
Indoor/outdoor
communication, receiving
error
2-time fl ash
Outdoor power system
2.5 seconds
OFF
3-time fl ash
Discharge temperature
2.5 seconds
thermistor
OFF
Defrost thermistor
Fin temperature thermistor
P.C. board temperature
thermistor
Ambient temperature
thermistor
Outdoor heat exchanger
temperature thermistor
4-time fl ash
Overcurrent
2.5 seconds
OFF
Compressor synchronous
abnormality (Compressor
start-up failure protection)
5-time fl ash
Discharge temperature
2.5 seconds
OFF
6-time fl ash
High pressure
2.5 seconds
OFF
7-time fl ash
Fin temperature/ P.C. board
2.5 seconds
temperature
OFF
8-time fl ash
Outdoor fan motor
2.5 seconds
OFF
9-time fl ash
Nonvolatile memory data
2.5 seconds
OFF
Power module
10-time fl ash
Discharge temperature
2.5 seconds
OFF
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).

OBH532E

LED indication
(Outdoor P.C. board)
Any signals from the inverter P.C.
board cannot be received normally for
3 minutes.
Although the inverter P.C. board sends
signal "0", signal "1" has been received
30 consecutive times.
Overcurrent protection cut-out oper-
ates 3 consecutive times within 1
minute after the compressor gets
started.
1-time fl ash every
Thermistor shorts or opens during
2.5 seconds
compressor running.
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
2-time fl ash
2.5 seconds OFF
11-time fl ash
Large current fl ows into the intelligent
2.5 seconds OFF
power module (IPM)/ IGBT module
(IC700)/ power module (IPM). 1.
12-time fl ash
Waveform of compressor current is
2.5 seconds OFF
distorted.
Temperature of discharge temperature
thermistor exceeds 116°C, compressor
stops.
Compressor can restart if discharge
temperature thermistor reads 100°C or
less 3 minutes later.
Temperature of indoor coil thermistor
exceeds 70°C in HEAT mode.
Temperature of outdoor heat
exchanger temperature thermistor
exceeds 70°C in COOL mode.
7-time fl ash
Temperature of fi n temperature
2.5 seconds OFF
thermistor on the inverter P.C. board
exceeds 75 ~ 80°C, or temperature of
P.C. board temperature thermistor on
the inverter P.C. board exceeds 70 ~
75°C.
Outdoor fan has stopped 3 times in a
row within 30 seconds after outdoor
fan start-up.
5-time fl ash
Nonvolatile memory data cannot be
2.5 seconds OFF
read properly.
6-time fl ash
The interphase short circuit occurs
2.5 seconds OFF
in the output of the intelligent power
module (IPM)/ IGBT module (IC700)/
power module (IPM). 1.
The compressor winding shorts circuit.
Temperature of discharge temperature
thermistor has been 50°C or less for
20 minutes.
1.
Intelligent power module (IPM): MUZ-GE25VA -
IGBT module (IC700): MUZ-GE60/71/80VAD
Power module (IPM): Other models
Condition
•Refer to 11-5.
to check miswiring and
serial signal error.
•Refer to 11-5.
to check miswiring and
serial signal error.
Reconnect
connectors.
Refer to 11-5.
to check inverter/
compressor".
Check the stop valve.
Refer to 11-5.
"Check of outdoor
thermistors".
Defective outdoor
thermistors can be
identifi ed by checking
the blinking pattern of
LED.
Reconnect
compressor connector.
Refer to 11-5. "How
to check inverter/
compressor".
Check the stop valve.
Reconnect
compressor connector.
Refer to 11-5. "How
to check inverter/
compressor".
Check the refrigerant
circuit and the
refrigerant amount.
Refer to 11-5. "Check
of LEV".
Check the refrigerant
circuit and the
refrigerant amount.
Check the stop valve.
Check around the
outdoor unit.
Check the outdoor unit
air passage.
Refer to 11-5. "Check
of outdoor fan motor".
Refer to 11-5. "Check
of outdoor fan motor".
Refer to 11-5. "Check
of inverter P.C. board".
Replace the inverter
P.C. board.
Refer to 11-5.
to check inverter/
compressor".
Refer to 11-5. "Check
of LEV".
Check the refrigerant
circuit and the
refrigerant amount.
68
Indoor/outdoor
unit failure
Remedy
mode recall
recall function
function
How
How
"How
"How
, MUZ-GE35/50VA
A1
Outdoor unit