Kidde P4010ACLEDSCA User Manual page 18

Table of Contents

Advertisement

8. Alarm Visual and Audible Indicators
Operational Mode
Initiating Alarm
(Multiple alarms in
an Interconnected
system)
Low Battery
Fault Mode
End of Unit Life
End of Unit Life, Hush
Mode
End of Unit Life,
(30 days after End of
Life chirps begin)
If you require further information please contact Product Support at
1-800-880-6788 or write us at: Kidde Canada Inc., P.O. Box 40, Apsley, ON
K0L 1A0 or visit us on the web at www.kiddecanada.com.
Visual
Indications
Green LED blinks once per
second indicating that this
is the unit initiating the
alarm in an interconnected,
multiple alarm, system.
Red LED blink in time
with alarm pattern.
Strobe will flash 1 time
per second.
AC power must be applied -
strobe will not operate with
DC Only power applied.
Amber LED blink 2 times
per second – AC Power
applied
Red LED blink in time
with unit chirp every
60s. Battery backup
(DC only).
Red LED will blink in time
with unit chirp every 30
seconds. Separate from
the fault blink, the amber
LED will also flash a fault
code every 30 seconds.
The fault code can be 2 to
14 flashes depending on
the fault type.
Red LED blinks in time
with unit chirp, 2 times
every 30 seconds.
Red LED blinks once
every 2 seconds.
Red LED will blink in time
with unit chirp 2 times
every 30 seconds.
Audible
Indications
3 long beeps, voice mes-
sage "Fire! Feu!",3 long
beeps, repeating.
AC Power applied – Unit
will chirp once a minute
followed by the voice
message "Low Battery.
Pile Faible"
Battery Backup – Unit will
chirp once a minute, the
voice message "Low Bat-
tery. Pile Faible" will occur
once every 15 minutes.
Unit will chirp every
30 seconds.
Unit will chirp 2 times
every 30 seconds.
None, End of Unit Life
chirps silenced.
Unit will chirp 2 times
every 30 seconds.
Note:
Green LED operation of
non-initiating alarms:
AC power applied: On
continuously.
DC Only power applied:
Flash once every minute.
All P4010ACLEDSCA
strobes in an
interconnected
system will flash in
synchronization.
Ambient Light Sensor
Feature – Inhibits Low
Battery chirps during
the night.
The alarm should be
replaced as soon as
possible. See section
11, Deactivation of
Alarm, before disposing
of alarm.
Remove, deactivate, and
replace alarm as soon as
possible.
Ambient Light Sensor -
Inhibits End of Unit Life
chirps at night for the
first 30 days of the End of
Unit Life period.
Remove, deactivate, and
replace alarm as soon as
possible."
Pressing the Test/Hush
button will silence the
chirps for 3 days at a
time for a maximum of
30 days. After 30 days,
End of Unit Life chirps
cannot be silenced.
Remove, deactivate, and
replace alarm as soon as
possible.
Remove, deactivate, and
replace alarm as soon as
possible.

Hide quick links: