6-2. Optional Auxiliary Power Receptacles

Simultaneous Welding And Auxiliary Power
Weld Current
Amperes
250
225
200
150
100
50
0
Output
120 V
Watts
Receptacle
Receptacle
Amperes
Amperes
3500
31
15.5
4260
39
5140
46
6700
60
8000
62.4
31.2
8000
62.4
31.2
8000
62.4
31.2
1
240 V
19
23
30
Y If unit does not have GFCI re-
ceptacles,
use
GFCI-
protected extension cord.
.
Auxiliary power decreases as
weld current increases.
Combined output of all receptacles
limited to 8 kVA/kW rating of the
generator.
GFCI Receptacle Option
1
120 V 15 A AC GFCI Recep-
tacles GFCI2 and GFCI3
GFCI2 and GFCI3 supply 60 Hz
single-phase power at weld/power
speed. Maximum output from
GFCI2 or GFCI3 is 2.4 kVA/kW. Cir-
cuit breaker protection is the same
as standard receptacles.
If a ground fault is detected, the
GFCI Reset button pops out and
the circuit opens to disconnect the
faulty
equipment.
Check
damaged tools, cords, plugs, etc.
connected to the receptacle. Press
button to reset receptacle and
resume operation.
.
At least once a month, run
engine at weld/power speed
and press Test button to verify
GFCI is working properly.
Ref. ST-189 925-A