Superior DRT40ST40DMN Installation And Operation Instructions Manual page 9

Drt40 multi-view series direct-vent gas fireplaces
Table of Contents

Advertisement

Innovative Hearth Products
DRT40 Multi View Series Direct Vent Gas Fireplace
EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS
D
E
V
B
L
C
Fixed
Closed
Openable
F
V
B
V
TERMINATION CAP
A Clearance above grade, veranda, porch, desk, or balcony
B Clearance to window or door that may be opened
C Clearance to permanently closed window
D Vertical clearance to ventilated soffit located above the
termination within a horizontal distance of 18" (458 mm)
E Clearance to unventilated soffit
F Clearance to outside corner
G Clearance to inside corner
H Clearance to each inside of center line extended above
meter / regulator assembly
I Clearance to service regulator vent outlet
J Clearance to nonmechanical air supply inlet to building or
the combustion air inlet to any other fireplace
K Clearance to a mechanical air supply inlet
L Clearance above paved sidewalk or paved diveway located
on public property
M Clearance under veranda, porch, deck or balcony
N Depth of alcove (maximum)
O Clearance to termination (alcove)
P Width of alcove (minimum)
Q Clearance to combustible above (alcove)
*
In accordance with the current CSA-B149.1 National Gas And Propane Installation Code
**
In accordance with the curent ANSI Z223.1/NFPA 54 National Fuel Gas Codes
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
*‡
Only permitted if veranda, porch, deck, or balcony is fully-open on a minimum two sides beneath the floor
See Figure 5
H
B
V
V
Openable Fixed
Closed
B
G
V
J
X
B
A
AIR SUPPLY INLET
G
GAS METER
RESTRICTED AREA
X
(TERMINATION PROHIBITED)
U.S. Installation **
12" (300 mm) **
6" (150 mm)
for fireplaces < 10,000 Btu/h (3 kW),
9" (230 mm)
for fireplaces > 10,000 Btu/h (3 kW), and < 50,000 Btu/h (15
kW),
12" (300 mm)
for fireplaces > 50,000 Btu/h (15 kW) **
9" (229 mm)
recommended to prevent window condensation
18" (458 mm)
12" (305 mm)
5" (127 mm)
minimum
6" (152 mm) minimum
36" (910 mm)
within a height of 15 ft above the meter / regulator assembly **
36" (910 mm)**
6" (150 mm)
for fireplaces < 10,000 Btu/h (3 kW),
9" (230 mm)
for fireplaces > 10,000 Btu/h (3 kW) and < 50,000 Btu/h (15 kW),
12" (300 mm)
for fireplaces > 50,000 Btu/h (15 kW)**
36" (910 mm) above if within 10 ft (3 m) horizontally **
84" (2130 mm) ‡
12" (300 mm) *‡
72" (1830 mm) **
6" (15.2 mm) **
36" (910 mm) **
18" (457 mm) **
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Inside Corner
G
V
I
Balcony with No Side Wall
G
V
M
G
M
V
V
V
K
X
A
Installation and Operation Instructions
900299-00, 08/2015
Outside Corner
Recessed Location
N
O
V
F
Balcony with Perpendicular Side Wall
M
V
Canadian Installation *
12" (300 mm) *
6" (150 mm)
for fireplaces < 10,000 Btu/h (3 kW),
12" (300 mm)
for fireplaces > 10,000 Btu/h (3 kW)
12" (305 mm)
recommended to prevent window
condensation
18" (458 mm)
12" (305 mm)
5" (127 mm)
minimum
6" (152 mm) minimum
36" (910 mm)
within a height of 15 ft above the meter /
regulator assembly *
36" (910 mm)*
6" (150 mm)
for fireplaces < 10,000 Btu/h (3 kW),
12" (300 mm)
for fireplaces > 10,000 Btu/h (3 kW)
72" (1830 mm) *
84" (2130 mm) ‡
12" (300 mm) *‡
72" (1830 mm) *
6" (15.2 mm)*
36" (910 mm) *
18" (457 mm) *
P
Q
V
9

Advertisement

Table of Contents
loading

Table of Contents